Set Appliance State:
Mains Power Off
Selector switch to Hot Water position
DHW temperature control set to MAX
Preheat OFF
DHW temperature control set to MAX
Preheat OFF
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Ensure the start up sequence has completed, the pump and fan have stopped and the boiler is showing 0.
Run the hot tap with a flow rate of 3 l/min.
The display should show "d" and the fan and pump should run.
Does the boiler react as described above?
Note:
If a fault code is displayed after running the tap click HERE.
Run the hot tap with a flow rate of 3 l/min.
The display should show "d" and the fan and pump should run.
Does the boiler react as described above?
Note:
If a fault code is displayed after running the tap click HERE.