Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Selector switch set to CH/DHW
CH temperature control set to MAX
Preheat switched OFF
Note.
Slightly move connectors until PCB connection strips
are exposed for voltage measurement
CH temperature control set to MAX
Preheat switched OFF
Note.
Slightly move connectors until PCB connection strips
are exposed for voltage measurement
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure for AC voltage across pin 2 (X1 connector PCB) and
main neutral (terminal block).
Expected voltage approximately 230 Vac.
main neutral (terminal block).
Expected voltage approximately 230 Vac.

Isolate as per TOPs P4
and refit as necessary