Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Selector switch set to DHW/CH
CH temperature control set to MAX
Preheat switched OFF
Attach temperature probes to flow and return pipes
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the appliance to ignite and run for central heating.
Observe the flow and differential temperatures.
At approximately 80°C flow temperature the boiler should shut down, without L1(overheat) fault code appearing, during this time the differential temperature should not exceed 30°C.
Note.
1. To speed up this test, reduce the heating circuit by turning off some radiators.
2. If a fault code other than L1 appears CLICK HERE.