Set Appliance State:
Mains Power Off
Turn Hot Water Tap On
Selector switch set to DHW
DHW temperature control set to MAX
Preheat switched OFF
DHW temperature control set to MAX
Preheat switched OFF
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow the appliance to ignite and run DHW demand.
With a flow rate as per the table is there a temperature rise of approximately 35°C and is operation satisfactory?
 
Note.
If the appliance has a flow regulator fitted, the draw off rate will be below
the rate specified above, which will result in a higher temperature rise.
With a flow rate as per the table is there a temperature rise of approximately 35°C and is operation satisfactory?
 
Note.
If the appliance has a flow regulator fitted, the draw off rate will be below
the rate specified above, which will result in a higher temperature rise.