Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Selector switch set to DHW
DHW temperature control set to MAX
Preheat switched OFF
DHW temperature control set to MAX
Preheat switched OFF
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Is the diverter valve is in the DHW position?
Note.
Location is behind the condensate trap, an inspection
mirror may help with observation.
Note.
Location is behind the condensate trap, an inspection
mirror may help with observation.