Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Preheat OFF
Attach temp probes to the main Flow and Return pipes to the primary Heat Exchanger
Note: Ensure a good connection is made with the flow & return pipes
or misdiagnosis will occur
Attach temp probes to the main Flow and Return pipes to the primary Heat Exchanger
Note: Ensure a good connection is made with the flow & return pipes
or misdiagnosis will occur
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow the boiler to fire for Hot Water and once it has reached
a reasonable operating temperature.
Measure the temperature of the main flow and return pipes to the primary
heat exchanger and ascertain temperature difference between them.
Expect a temperature differential of approx 24°C or less.
a reasonable operating temperature.
Measure the temperature of the main flow and return pipes to the primary
heat exchanger and ascertain temperature difference between them.
Expect a temperature differential of approx 24°C or less.