Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Ensure there is no demand for either CH or DHW
Preheat OFF
Gain access to the boilers main terminal strip
Preheat OFF
Gain access to the boilers main terminal strip
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage to Earth on the Frost input connection (far right, black and white wires) of the boilers main terminal strip.

Isolate as per TOPs P4
and refit as necessary