Set Appliance State:
Mains Power Off
Turn Hot Water Tap On
Boiler Mains Switch ON
Diverter valve located at the lower LH side of the appliance
Diverter valve located at the lower LH side of the appliance
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Is the diverter valve in the DHW position (lever forward)?
Note:
CH position - lever towards the back.
DHW position - lever towards the front.
If the diverter valve is in the correct position then it is advisable to repeat this test several times as the valve could be sticking.
Note:
CH position - lever towards the back.
DHW position - lever towards the front.
If the diverter valve is in the correct position then it is advisable to repeat this test several times as the valve could be sticking.