Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove diverter valve actuator, place in a safe position where the spindle can be observed
Use insulation Mat as required
Use insulation Mat as required
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Turn a hot water tap ON.
After 30 seconds:
With the aid of a screwdriver confirm the actuator spindle
is in the recessed position (DHW position)?
After 30 seconds:
| Isolate Mains Power to appliance as per TOP's P4 |
With the aid of a screwdriver confirm the actuator spindle
is in the recessed position (DHW position)?
Isolate as per TOPs P4
and refit as necessary