Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Adjust DHW flow rate to approx. 5 litres/min
DHW Temperature Control set to approx. 12 o'clock position
Attach pressure gauge to gas valve pressure outlet test point
DHW Temperature Control set to approx. 12 o'clock position
Attach pressure gauge to gas valve pressure outlet test point
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow burner to ignite and establish.
As the hot water starts to reach temperature does the burner pressure modulate down to maintain temperature?
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
As the hot water starts to reach temperature does the burner pressure modulate down to maintain temperature?
Note:
When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Isolate as per TOPs P4
and refit as necessary