Set Appliance State:
Mains Power Off
Turn Hot Water Tap On
Set flow rate to 11.7 litres a minute
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow burner to ignite and establish.
Allow the boiler to run for at least 2 minutes.
Does the same fault code reappear? (Shown to the right)
Does the heating flow pipe remain cold?
Note:
If a different fault code occurs click HERE to return to fault code page.
Allow the boiler to run for at least 2 minutes.
Does the same fault code reappear? (Shown to the right)
Does the heating flow pipe remain cold?
Note:
If a different fault code occurs click HERE to return to fault code page.