IDEAL ISAR / EVO HE - RED TOP DIVERTER HEAD
GLOBALLY REPLACED
IDEAL ISAR / EVO HE - RED TOP DIVERTER HEAD
BOILER FRONT
PREHEAT SATISFACTORY
ENSURE SECONDARY HEA
CH DEMAND
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
DHW OPERATION
BOILER ON OFF SWITCH ON
BOILER DHW THERMOSTAT SET TO MAX
DHW BURNER MODULATION
SET THE DHW FLOW RATE AT THE TAP TO APPROXIMATELY 3.0 L/MIN
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
CH BURNER MODULATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CHOICE FULL DIAG OR FAULT CODE
THIS MODEL CONTAI
WATER IN IMPULSE TUBE
HEADER FOR IMPULSE TUBE INVESTIGATION
HEADER FOR FUSE INVESTIGATION
INTENTIONALLY BLANK HEADER FOR FUSE INVESTIGATION
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
PREHEAT INPUT CHECK
INPUT LINK
LINK FAULT
INPUT LINK
DHW BURNER MODULATION
THERMISTOR - BOILER CONTROL (FLOW)
DHW BURNER MODULATION
THERMISTOR - BOILER CONTROL (RETURN)
DHW BURNER MODULATION
USER CONTROL (DISPLAY UNIT)
OUT OF CALIBRATION
DHW THERMISTOR
PUMP RUNS PREHEAT
HARNESS - BOILER WIRING
LF FAULT99PRE HEATFCDIAG
LEAD - DETECTION
FAULT L E FAULT CODE DIAGNOSIS 3
ELECTRODE - FLAME DETECTION
LF FAULT CODE
ELECTRODE - FLAME DETECTION
PREHEAT FLAME SENSEFCDIAG
BURNER
RESTRICTED OR BLOCKED 5
TRAP AND SEAL
HF FAULTPRE HEATFCDIAG
LEAD - DETECTION
HF FAULTFAULT L E FAULT CODE DIAGNOSIS
ELECTRODE - FLAME DETECTION
RADS COOL CH OPPREHEAT
DHW THERMISTOR
OPEN CIRCUIT FAULT L_E FC DIAG
THERMOSTAT - OVERHEAT
PRE HEATFCDIAG
LEAD - DETECTION
FAULT L E FAULT CODE DIAGNOSIS
ELECTRODE - FLAME DETECTION
PREHEAT SATISFACTORY
CARTRIDGE - DIVERTER VALVE
BLOCKED PREHEAT SAT
PLATE - HEAT EXCHANGER
DHW QUIET OPERATION RADIATORS WARM
CARTRIDGE - DIVERTER VALVE
BLOCKED DHW OP
PLATE - HEAT EXCHANGER
RADS COOL CH OP
THERMISTOR - BOILER CONTROL (FLOW)
REACHES TEMP RADS COOL
CARTRIDGE - DIVERTER VALVE
CH OPERATION
PUMP
PASSING CH OPPREHEAT
TAPS
OUT OF CALIBRATION 7
DHW THERMISTOR
OVERHEAT SECTION
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 1
THERMISTOR - BOILER CONTROL (FLOW)
OVERHEAT
SYSTEM FILL AND VENT
PUMP VOLTAGE
PCB - PRIMARY CONTROLS
FAULTYLARESET
PUMP
OVERHEAT OPERATION OH LA RESET
DHW THERMISTOR
OVERHEAT SECTIONH_2 FC DIAGOHLARESET
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT SECTIONOHLARESET
THERMISTOR - BOILER CONTROL (FLOW)
POTSOHLARESET
USER CONTROL (DISPLAY UNIT)
OVERHEAT PROBLEMOHLARESETH9OH
PLATE - HEAT EXCHANGER
FAULT CODE DIAG
FAN
FAULT HE
HARNESS FAN
OVERHEAT OPERATION LA H9
DHW THERMISTOR
OVERHEAT SECTION 2
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 2
THERMISTOR - BOILER CONTROL (FLOW)
PUMP VOLTAGE 2
PCB - PRIMARY CONTROLS
FAULTYLARESETHA
PUMP
OVERHEAT OPERATION OH LA RESET 2
DHW THERMISTOR
OVERHEAT SECTIONH_2 FC DIAGOHLARESETHA
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT SECTIONOHLARESETHA
THERMISTOR - BOILER CONTROL (FLOW)
POTSOHLARESETHA
USER CONTROL (DISPLAY UNIT)
OVERHEAT PROBLEMOHLARESETH9OHHA
PLATE - HEAT EXCHANGER
OVERHEAT OPERATION
DHW THERMISTOR
OVERHEAT SECTION 3
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 3
THERMISTOR - BOILER CONTROL (FLOW)
WATER
GAS VALVE
DRIED ALL WORKING
IMPULSE TUBE WATER INGRES
L9
SYSTEM FILL AND VENT
CONNECTOR FAULT POWER UP
MAINS CONNECTOR
POWER UP
MAINS SWITCH C/W HARNESS
BLANK DISPLAY
PCB - PRIMARY CONTROLS AND FAN
NO DISPLAY
PCB - PRIMARY CONTROLS AND FAN
BLANK DISPLAY
PCB/ USER CONTROL HARNESS
LF FAULT CODE
HEAT ENGINE
FALT CODE LF2
INSULATION - COMBUSTION CHAMBER
LF FAULT CODE
ELECTRODE - IGNITION (GAP)
FAULT CODE L-F
IMPULSE TUBE
FAULT CODE L_F
INJECTOR & HOUSING
RESTRICTED OR BLOCKED 7
TRAP AND SEAL
FAULT CODE LF
BURNER
FALT CODE LF
INSULATION - COMBUSTION CHAMBER
LF CODE
FLUE WAYS
FLASHES LA OR HA
THERMISTOR - DRY FIRE
NO INVESTIGATIONLA
BOILER OVERHEAT
NOT RESETLA
THERMOSTAT - OVERHEAT
OVERHEAT OPERATION 2
DHW THERMISTOR
OVERHEAT SECTION 4
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 4
THERMISTOR - BOILER CONTROL (FLOW)
FLASHES LA OR HA WILL NOT RESET
THERMISTOR - DRY FIRE
OVERHEATLA
REDIRECTS
OVERHEAT OPERATION 3
DHW THERMISTOR
OVERHEAT SECTION 5
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 5
THERMISTOR - BOILER CONTROL (FLOW)
RESETS SHOWS 3 DASHES
THERMISTOR - DRY FIRE
RESETS SHOWS 3 DASHES 1
THERMISTOR - DRY FIRE
FC DIAG H_N
POLARITY REVERSAL
FLASHES H9 OR L9
THERMISTOR - DRY FIRE
NO INVESTIGATIONLAH9
BOILER OVERHEAT
NOT RESETLAH9
THERMOSTAT - OVERHEAT
OVERHEAT OPERATION 4
DHW THERMISTOR
OVERHEAT SECTION 6
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 6
THERMISTOR - BOILER CONTROL (FLOW)
FLASHES H9 OR L9 WILL NOT RESET
THERMISTOR - DRY FIRE
OVERHEATLAH9
REDIRECTS
OVERHEAT OPERATION 5
DHW THERMISTOR
OVERHEAT SECTION 7
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAGOVERHEAT 7
THERMISTOR - BOILER CONTROL (FLOW)
H9 OR L9 RESETS SHOWS 3 DASHES
THERMISTOR - DRY FIRE
H9 OR L9 RESETS SHOWS 3 DASHES 1
THERMISTOR - DRY FIRE
RED DASH FC DIAG
PCB/ USER CONTROL HARNESS
DASH DOT FAULT CODE
USER CONTROL INTERFACE
DOT DASH FAULT CODE
USER CONTROL (DISPLAY UNIT)
OVERHEATLAH93 DASHES
REDIRECTS
OVERHEAT OPERATION 6
DHW THERMISTOR
OVERHEAT SECTION 8
THERMISTOR - BOILER CONTROL (RETURN)
CH BURNER MODULATION
USER CONTROL (DISPLAY UNIT)
H_1 FC DIAGOVERHEAT 8
THERMISTOR - BOILER CONTROL (FLOW)
3 DASHES
THERMISTOR - DRY FIRE
3 DASHES 1
THERMISTOR - DRY FIRE
99PRE HEATFCDIAG
LEAD - DETECTION
FAULT L E FAULT CODE DIAGNOSIS 2
ELECTRODE - FLAME DETECTION
SPARKING PRESENT
ELECTRODE - IGNITION (GAP)
BURNER DOES NOT IGNITE
IMPULSE TUBE
BURNER DOES NOT IGNITE
INJECTOR & HOUSING
RESTRICTED OR BLOCKED 10
TRAP AND SEAL
BURNER DOES NOT IGNITE
BURNER
BURNER DOES NOT IGNITE
INSULATION - COMBUSTION CHAMBER
BURNER DOES NOT IGNITE
FLUE WAYS
BURNER IGNITES BUT DOES NOT ESTABLISH
GAS INLET PRESSURE
BURNER ESTABLISHES PRE HEAT
LEAD - DETECTION
BURNER ESTABLISHES (PREHEAT)
ELECTRODE - FLAME DETECTION
GAP
ELECTRODE - FLAME DETECTION (GAP)
RESTRICTED OR BLOCKED 9
TRAP AND SEAL
BURNER ESTABLISHES (PREHEAT)
BURNER
BURNER IGNITES BUT DOES NOT ESTABLISH
INSULATION - COMBUSTION CHAMBER
BURNER IGNITES BUT DOES NOT ESTABLISH
HEAT ENGINE
BURNER ESTABLISHES (PREHEAT)
TURRET GASKET
RADS TOO COOL BOILER TO TEMP
CARTRIDGE - DIVERTER VALVE
BOILER FIRING AFTER PREHEAT WITH NO DEMAND
THERMISTOR - BOILER CONTROL (FLOW)
ON WITH NO DEMAND
THERMISTOR - BOILER CONTROL (RETURN)
H THEN F OR L THEN F DOT
LEAD - DETECTION
L THEN F OR H THEN F DOT
ELECTRODE - FLAME DETECTION
OUT OF CALIBRATION 4
DHW THERMISTOR
OUT OF CALIBRATION 5
DHW THERMISTOR
PUMP DOES NOT RUN
DHW THERMISTOR
PREHEAT SATISFACTORY
PCB - PRIMARY CONTROLS
PREHEAT SATISFACTORY
HARNESS - BOILER WIRING
DHW QUIET OPERATION RADIATORS WARM
PCB - PRIMARY CONTROLS
DHW RADS WARM
HARNESS - BOILER WIRING
DOES NOT RECOGNISE DEMAND
HARNESS FAN
DAMAGED L8
HARNESS FAN
FAN DOES NOT RUN 3 L8
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 4 L8
PCB - PRIMARY CONTROLS AND FAN
POWER FROM PCB L8
HARNESS FAN
PUMP RUNS (PREHEAT)
THERMISTOR - BOILER CONTROL (FLOW)
NO FAN L8
HARNESS FAN
FAN DOES NOT RUN L8
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 2 L8
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN L8
HARNESS FAN
CH BOILER TO TEMP
HARNESS - BOILER WIRING
DIVERTER VOLTAGE CH OP
PCB - PRIMARY CONTROLS
RADS COOL CH OP
DHW THERMISTOR
PUMP RUNS (PREHEAT)
THERMISTOR - BOILER CONTROL (RETURN)
PASSING CH OP
TAPS
PUMP RUNS (PREHEAT)
THERMISTOR - DRY FIRE
PUMP RUNS (PREHEAT)
DHW THERMISTOR
RESTRICTED OR BLOCKED
TRAP AND SEAL
RESTRICTED OR BLOCKED 2
TRAP AND SEAL
LOW 2
GAS INLET PRESSURE
RESTRICTED OR BLOCKED
IMPULSE TUBE
LEAKING CAUSING BAFFLING ETC
TURRET GASKET
DAMAGED OR BLOCKED
BURNER
COLLAPSED IN AFFECTING COMBUSTION
INSULATION - COMBUSTION CHAMBER
RESTRICTED OR BLOCKED
FLUE WAYS
RESTRICTED OR BLOCKED 2
INJECTOR & HOUSING
RUNNING SLOW / WEAK
PUMP
RADS COOL CH OP 2
THERMISTOR - BOILER CONTROL (FLOW)
SHUTS DOWN PREMATURELY
CARTRIDGE - DIVERTER VALVE
CH BOILER TO TEMP 2
HARNESS - BOILER WIRING
DIVERTER VOLTAGE CH OP 2
PCB - PRIMARY CONTROLS
OUT OF CALIBRATION 6
DHW THERMISTOR
PASSING CH OP 2
TAPS
SHUTS DOWN PREMATURELY 2
CARTRIDGE - DIVERTER VALVE
CH OPERATION 2
PUMP
PREMATURE SHUTDOWN
USER CONTROL (DISPLAY UNIT)
CH OPERATION
TURRET GASKET
RESTRICTED OR BLOCKED 8
TRAP AND SEAL
MAINS FUSE INVESTIGATION
REDIRECTS
POWER UP
FUSE MAIN PCB F1
FUSE BLOW
GAS VALVE
ELECTRICAL SHORT
DIVERTER VALVE HEAD
FUSE BLOWN 4
HARNESS - BOILER WIRING
FUSE BLOWN 3
HARNESS - BOILER WIRING
KETTLING
SYSTEM FILL AND VENT
AIR IN CH CIRCUIT
SYSTEM FILL AND VENT
FAULT LF
IMPULSE TUBE
FAULT FURTHER INVESTIGATION LF
THERMOSTAT - OVERHEAT
FAULT LF
GAS VALVE
OVERHEAT NOT GONE
PCB - PRIMARY CONTROLS
RESTRICTED OR BLOCKED 3
TRAP AND SEAL
FAULT LF BURNER DOES NOT IGNITE
IMPULSE TUBE
FAULT FURTHER INVESTIGATION LF BURNER DOES NOT IGNITE
THERMOSTAT - OVERHEAT
FAULT LF BURNER DOES NOT IGNITE
GAS VALVE
OVERHEAT NOT GONE BURNER DOES NOT IGNITE
PCB - PRIMARY CONTROLS
RESTRICTED OR BLOCKED 3 BURNER DOES NOT IGNITE
TRAP AND SEAL
NO GAS DROP
INJECTOR & HOUSING
BURNER DOES NOT IGNITE 2
INJECTOR & HOUSING
H_4 FC DIAG 2
THERMISTOR - DRY FIRE
FAULT H4
PCB - PRIMARY CONTROLS
FC DIAG H_4 NOT FILLED AND VENTED
SYSTEM FILL AND VENT
SPARK GEN BURNER IGNITES PREHEAT 3
PCB - PRIMARY CONTROLS & HARNESS BOILER
IGNITION BURNER IGNITES PREHEAT NO SPARKING 4
ELECTRODE - IGNITION
IGNITION BURNER IGNITES PREHEAT NO SPARK 3
ELECTRODE - IGNITION
SPARK GEN BURNER IGNITES PREHEAT 2
PCB - PRIMARY CONTROLS & HARNESS BOILER
IGNITION BURNER IGNITES PREHEAT NO SPARKING 2
ELECTRODE - IGNITION
IGNITION BURNER IGNITES PREHEAT NO SPARK
ELECTRODE - IGNITION
BURNER IGNITES PREHEAT NO SPARK2
GAS VALVE
BURNER IGNITES PREHEAT NO SPARK2
HARNESS - BOILER WIRING
BURNER IGNITES PREHEAT NO SPARK
HARNESS - BOILER WIRING
BURNER IGNITES PREHEAT NO SPARK
GAS VALVE
DHW OPERATION POOR TEMP RISE
THERMISTOR - BOILER CONTROL (FLOW)
DHW OPERATION POOR TEMP RISE
THERMISTOR - BOILER CONTROL (RETURN)
DHW OPERATION POOR TEMP RISE
THERMISTOR - DRY FIRE
OUT OF CALIBRATION 3
DHW THERMISTOR
POOR DHW
USER CONTROL (DISPLAY UNIT)
LOW
GAS INLET PRESSURE
PASSING MIXER TAP
PLUMBING ISSUE
RESTRICTED OR BLOCKED
INJECTOR & HOUSING
RESTRICTED OR BLOCKED - POOR DHW
TRAP AND SEAL
RESTRICTED POOR DHW
BURNER
DAMAGED
HARNESS FAN
FAN DOES NOT RUN 3
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 4
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN
THERMISTOR - BOILER CONTROL (FLOW)
FAN DOES NOT RUN
THERMISTOR - BOILER CONTROL (RETURN)
POWER FROM PCB
HARNESS FAN
NO FAN
HARNESS FAN
FAN DOES NOT RUN
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 2
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 2
THERMISTOR - BOILER CONTROL (FLOW)
FAN DOES NOT RUN 2
THERMISTOR - BOILER CONTROL (RETURN)
FAN DOES NOT RUN
HARNESS FAN
DHW NOISY
HEAT ENGINE
DHW OPERATION
PUMP
DHW OPERATION
THERMISTOR - BOILER CONTROL (FLOW)
DHW OPERATION
THERMISTOR - DRY FIRE
OUT OF CALIBRATION 2
DHW THERMISTOR
DHW OPERATION
THERMOSTAT - OVERHEAT
DHW OPERATION
THERMISTOR - BOILER CONTROL (RETURN)
RESTRICTED OR BLOCKED 6
TRAP AND SEAL
DHW FLOW RATE
FLOW RESTRICTOR
H_2 FC DIAG
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAG
THERMISTOR - BOILER CONTROL (FLOW)
PREHEATIGNITES BUT DOES NOT ESTABLISHFCDIAG
GAS INLET PRESSURE
INCORRECT POSITION
JUMPER SETTINGS
PREHEAT SATISFACTORY
HEAT ENGINE
CH INPUT
MULTI FAULT PCB
EXTERNAL CONTROL
HARNESS INPUT
EXTERNAL CONTROL
HARNESS EXTERNAL CONTROL
DHW BURNER MODULATION
PCB - PRIMARY CONTROLS
PUMP RUNS THEN STOPS
PCB - PRIMARY CONTROLS
HF FAULTL_E FC DIAG
PCB - PRIMARY CONTROLS
L_E FC DIAG
PCB - PRIMARY CONTROLS
LETBY PREHEAT
CARTRIDGE - DIVERTER VALVE
LETBY DHW OPERATION
CARTRIDGE - DIVERTER VALVE
PRE HEAT STUCK CH OPPREHEAT
PCB - PRIMARY CONTROLS
OVERHEAT TEMP
PCB - PRIMARY CONTROLS
OVERHEATING 1
HARNESS - BOILER WIRING
OVERHEATING 21
HARNESS - BOILER WIRING
OVERHEATING 11
HARNESS - BOILER WIRING
OVERHEATING 9
HARNESS - BOILER WIRING
OVERHEATING 29
HARNESS - BOILER WIRING
OVERHEATING 19
HARNESS - BOILER WIRING
RUN OKOH
BOILER OVERHEAT
OH SECTIONOHLARESETH9OH
MULTI FAULT PCB
FAULTYOHLARESETH9OH
HARNESS EXTERNAL CONTROL
NOISY
HEAT ENGINE
FAULT HE
PCB - PRIMARY CONTROLS
OVERHEAT TEMP 2
PCB - PRIMARY CONTROLS
OVERHEATING 2
HARNESS - BOILER WIRING
OVERHEATING 22
HARNESS - BOILER WIRING
OVERHEATING 12
HARNESS - BOILER WIRING
OVERHEATING 10
HARNESS - BOILER WIRING
OVERHEATING 30
HARNESS - BOILER WIRING
OVERHEATING 20
HARNESS - BOILER WIRING
RUN OKOHHA
BOILER OVERHEAT
NOISY 2
HEAT ENGINE
OH SECTIONOHLARESETH9OHHA
MULTI FAULT PCB
FAULTYOHLARESETH9OHHA
HARNESS EXTERNAL CONTROL
OVERHEAT TEMP 23 DASHES
PCB - PRIMARY CONTROLS
OVERHEATING 3
HARNESS - BOILER WIRING
OVERHEATING 23
HARNESS - BOILER WIRING
OVERHEATING 13
HARNESS - BOILER WIRING
IMPULSE TUBE
WATER LEAK AND GAS VALVE
IMPULSE TUBE
WATER LEAK
PUMP RUNS (PREHEAT)
PUMP
FROM PCB
HARNESS - BOILER WIRING
PUMP NOT RUNNING ON PREHEAT
PCB - PRIMARY CONTROLS
DHW FC DIAG PUMP NOT RUNNING STARTUP
HARNESS - BOILER WIRING
MAINS CONNECTOR PCB POWER UP
HARNESS - BOILER WIRING
BLANK DISPLAY
HARNESS - BOILER WIRING
NO DISPLAY
USER CONTROL (DISPLAY UNIT)
NO DISPLAY
PCB - PRIMARY CONTROLS
BLANK DISPLAY BLUE PCB FITTED
USER CONTROL (DISPLAY UNIT)
BLANK DISPLAY
PCB - PRIMARY CONTROLS
BLANK DISPLAY
USER CONTROL INTERFACE
LF FAULT99L_E FC DIAG
PCB - PRIMARY CONTROLS
PREHEATFCDIAG
GAS INLET PRESSURE
INCORRECT MIX 1
GAS VALVE
FLASHES LA OR HA
HARNESS - BOILER WIRING
INVESTIGATIONLA
REDIRECTS
OVERHEATLA
HARNESS - BOILER WIRING
OVERHEAT TEMP 3
PCB - PRIMARY CONTROLS
OVERHEATING 4
HARNESS - BOILER WIRING
OVERHEATING 24
HARNESS - BOILER WIRING
OVERHEATING 14
HARNESS - BOILER WIRING
FLASHES LA OR HA WILL NOT RESET
HARNESS - BOILER WIRING
OVERHEATLA
BOILER OVERHEAT
OVERHEAT TEMP 4
PCB - PRIMARY CONTROLS
OVERHEATING 5
HARNESS - BOILER WIRING
OVERHEATING 25
HARNESS - BOILER WIRING
OVERHEATING 15
HARNESS - BOILER WIRING
RESETS SHOWS 3 DASHES
HARNESS - BOILER WIRING
RESETS SHOWS 3 DASHES 1
HARNESS - BOILER WIRING
FLASHES H THEN N
PCB - PRIMARY CONTROLS
FLASHES H9 OR L9
HARNESS - BOILER WIRING
INVESTIGATIONLAH9
REDIRECTS
OVERHEATLAH9
HARNESS - BOILER WIRING
OVERHEAT TEMP 5
PCB - PRIMARY CONTROLS
OVERHEATING 6
HARNESS - BOILER WIRING
OVERHEATING 26
HARNESS - BOILER WIRING
OVERHEATING 16
HARNESS - BOILER WIRING
FLASHES H9 OR L9 WILL NOT RESET
HARNESS - BOILER WIRING
OVERHEATLAH9
BOILER OVERHEAT
OVERHEAT TEMP 6
PCB - PRIMARY CONTROLS
OVERHEATING 7
HARNESS - BOILER WIRING
OVERHEATING 27
HARNESS - BOILER WIRING
OVERHEATING 17
HARNESS - BOILER WIRING
H9 OR L9 RESETS SHOWS 3 DASHES
HARNESS - BOILER WIRING
H9 OR L9 RESETS SHOWS 3 DASHES 1
HARNESS - BOILER WIRING
RED DASH
PCB - PRIMARY CONTROLS
OVERHEATLAH93 DASHES
BOILER OVERHEAT
OVERHEAT TEMP 7
PCB - PRIMARY CONTROLS
CH BURNER MODULATION
PCB - PRIMARY CONTROLS
OVERHEATING 8
HARNESS - BOILER WIRING
OVERHEATING 28
HARNESS - BOILER WIRING
OVERHEATING 18
HARNESS - BOILER WIRING
3 DASHES
HARNESS - BOILER WIRING
3 DASHES 1
HARNESS - BOILER WIRING
FAN HUNTS
PCB - PRIMARY CONTROLS
PRESSURE DROPS AWAY
GAS INLET PRESSURE
CH DEMAND
PCB - PRIMARY CONTROLS
WRONG MIX 1
GAS VALVE
BURNER IGNITES BUT DOES NOT ESTABLISH
PCB - PRIMARY CONTROLS
ON WITH NO DEMAND
PCB - PRIMARY CONTROLS
FAULT HF
PCB - PRIMARY CONTROLS
DOES NOT RECOGNISE DEMAND
HARNESS - BOILER WIRING
HB OR LB FAULT CODE
USER CONTROLS
STICKING
DIVERTER VALVE HEAD
PREHEAT SATISFACTORY
DIVERTER VALVE HEAD
TEMP RISE POOR RADS WARM
DIVERTER VALVE HEAD
DHW OPERATION
DIVERTER VALVE HEAD
FAN DOESNT RUN L8
PCB - PRIMARY CONTROLS
FAN NOT RUN L8
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB L8
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB FITTED L8
PCB - PRIMARY CONTROLS
CH OPERATION
DIVERTER VALVE HEAD
PRE HEAT STUCK CH OP
PCB - PRIMARY CONTROLS
BOILER CYCLING
PCB - PRIMARY CONTROLS
RESTRICTED OR BLOCKED
PLATE - HEAT EXCHANGER
RESTRICTED OR BLOCKED
HEAT ENGINE
WRONG MIX 2
GAS VALVE
CH OPERATION 2
DIVERTER VALVE HEAD
PRE HEAT STUCK CH OP 2
PCB - PRIMARY CONTROLS
PREMATURE SHUTDOWN OR BOILER DOESNT FIRE
PCB - PRIMARY CONTROLS
POWER UP
FUSE MAINS
PCB FUSE INVESTIGATION
REDIRECTS
FUSE BLOWN
HARNESS FAN
FUSE BLOWN 2
HARNESS - BOILER WIRING
FUSE BLOWN
HARNESS - BOILER WIRING
PCB - FUSE BLOWN
PCB - PRIMARY CONTROLS (FUSE)
FUSE BLOWN
SPARK GENERATOR
BLOWING FUSES
PUMP
FAULT CODE L-F
THERMOSTAT - OVERHEAT
FAULT CODE LF
HARNESS - BOILER WIRING
FAULT CODE L-F BURNER DOES NOT IGNITE
THERMOSTAT - OVERHEAT
FAULT CODE LF BURNER DOES NOT IGNITE
HARNESS - BOILER WIRING
MECHANICAL
GAS VALVE
MECHANICAL BURNER DOES NOT IGNITE
GAS VALVE
FLUE FC DIAG 2
HARNESS - BOILER WIRING
FAULT CODE H4
FAULT CODE RESET - RETEST APPLIANCE
NO SPARKING 3
PCB - PRIMARY CONTROLS & SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 3
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 3
LEAD - IGNITION
BURNER IGNITES PREHEAT NO SPARK4
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 4
LEAD - IGNITION
NO SPARKING 2
PCB - PRIMARY CONTROLS & SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 2
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 2
LEAD - IGNITION
BURNER IGNITES PREHEAT NO SPARK
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK
LEAD - IGNITION
BLANK DISPLAY 2
PCB AND FAN HARNESS
BLANK DISPLAY
PCB AND FAN HARNESS
FAN RUNS NO SPARK
HARNESS - BOILER WIRING
NO SPARKING 4
PCB - PRIMARY CONTROLS & SPARK GENERATOR
FAN RUNS NO SPARK 2
HARNESS - BOILER WIRING
NO SPARKING
PCB - PRIMARY CONTROLS & SPARK GENERATOR
FAULT H3
DHW SENSOR - PCB
DHW NOT RECOGNISED
DHW SENSOR - PCB
RESTRICTED OR BLOCKED POOR TEMP RISE
PLATE - HEAT EXCHANGER
RESTRICTED OR BLOCKED POOR TEMP RISE
HEAT ENGINE
BOILER CYCLING POOR TEMP RISE
PCB - PRIMARY CONTROLS
FAN DOESNT RUN
PCB - PRIMARY CONTROLS
FAN NOT RUN
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB FITTED
PCB - PRIMARY CONTROLS
DHW NOISY
PLATE - HEAT EXCHANGER
CH OPERATION
EXPANSION VESSEL
PREHEAT SATISFACTORY
PLATE - HEAT EXCHANGER
DHW FLOW RATE
PLATE - HEAT EXCHANGER
DHW FC DIAG
HARNESS - BOILER WIRING
H_2 FC DIAG
PCB - PRIMARY CONTROLS
RETURN FC DIAG
HARNESS - BOILER WIRING
H_1 FC DIAG
PCB - PRIMARY CONTROLS
FLOW FC DIAG
HARNESS - BOILER WIRING
FLASHES H THEN 5
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
BOILER DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION
BOILER KETTLES
CHARACTERISTIC TEST FROM CH OPERATION
FLASHES H9 OR L9
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
1 DASH AND/OR DOT
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
PREHEAT DOES NOT SWITCH OFF OR COMES ON TOO FREQUENTLY, RADS REMAIN COOL
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
3 DASHES
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
WILL NOT RESET
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
RESETS _SHOWS THREE DASHES
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
SYSTEM KETTLES (O/H)
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
SYSTEM DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
WILL NOT RESET
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
RESETS _SHOWS THREE DASHES
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
SYSTEM KETTLES (O/H)
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
SYSTEM DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
GAS FLOW PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM GAS FLOW
GAS FLOW DIPS BUT STILL NO IGNITION
CHARACTERISTIC TEST FROM GAS FLOW
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM FAN RUNS (PREHEAT)
FAN HUNTS RUNS SLOWS RUNS SLOWS
CHARACTERISTIC TEST FROM FAN RUNS (PREHEAT)
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITES (PREHEAT)
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM BURNER IGNITES (PREHEAT)
GAS FLOW PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM GAS FLOW
GAS FLOW DIPS BUT STILL NO IGNITION
CHARACTERISTIC TEST FROM GAS FLOW
PREHEAT SATISFACTORY - BOILER FIRES WITH NO DEMAND DISPLAY SHOWS C
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM PUMP RUNS (PREHEAT)
FLASHES L THEN F OR H THEN F (NOTE THE DOT AFTER THE F)
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
PUMP RUNS FOR APPROXIMATELY 5 SECONDS THEN STOPS
CHARACTERISTIC TEST FROM PUMP RUNS (PREHEAT)
HB OR LB (B WILL BE IN LOWER CASE)
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
DIVERTER VALVE STICKING
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE NOT IN CORRECT POSITION
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE STICKING
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE NOT IN CORRECT POSITION
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
RADIATORS HEAT UP DURING PREHEAT FUNCTION WITH NO CH DEMAND
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
BOILER KETTLING
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
DHW NOISY
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TEMPERATURE RISE INSUFFICIENT, RADS BEGIN TO HEAT
CHARACTERISTIC TEST FROM DHW OPERATION
BOILER CYCLING
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TEMPERATURE RISE INSUFFICIENT , RADS REMAIN COLD
CHARACTERISTIC TEST FROM DHW OPERATION
CH NOISY DURING OPERATION
CHARACTERISTIC TEST FROM CH OPERATION
BOILER FIRES FOR CH AND REACHES TEMPERATURE BUT RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM CH OPERATION
BOILER SHUTS DOWN PREMATURELY OR DOES NOT FIRE FOR CH
CHARACTERISTIC TEST FROM CH OPERATION
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM CH OPERATION
FLASHES L THEN E
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES LA OR HA
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES L THEN 8
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 1
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 2
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 3
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 4
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN F
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN N
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
NOISE WHEN MODULATING DOWN OR COMBUSTION NOISE DURING OPERATION
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
FLASHES H THEN E
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
30/07/2019 12:12:44 1907_0_50_1 08/08/2019 10:57:34
05/08/2019 15:13:48
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
PUMP VOLTAGE
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
PUMP VOLTAGE
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
REMOVE WATER FROM IMPULSE TUBE DOES BOILER NOW LIGHT
REMOVE WATER INGRESS FROM IMPULSE TUBE
FIT IMPULSE TUBE BACK TO GAS VALVE AND COMBUSTION CHAMBER
PUMP VOLTAGE AT PCB
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
FUSE RESISTANCE FUSED SPUR
REMOVE FUSE FROM FUSED SPUR
RESISTANCE ON OFF SWITCH
DISCONNECT THE ON/OFF SWITCH AT THE INLINE CONNECTOR
(AS HIGHLIGHTED OPPOSITE)
VOLTAGE AT MAIN PCB
LOWER MAIN PCB
DISCONNECT DISPLAY HARNESS FROM THE MAIN PCB
RESISTANCE FAN AND HARNESS
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN AND HARNESS
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE OVERHEAT AT PCB
REMOVE THE DIVERTER VALVE CONNECTOR FROM THE PCB
(SITUATED ON THE TOP OF THE PCB)
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE OVERHEAT AT PCB
REMOVE THE DIVERTER VALVE CONNECTOR FROM THE PCB
(SITUATED ON THE TOP OF THE PCB)
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
POTENTIOMETER RESISTANCE (CH)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
FAN VOLTAGE PERMANENT HALL SENSOR
NO DEMANDS FOR CH OR
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
DISPLAY SHOWS CORRECT DEMAND
IF PREHEAT ACTIVATES THEN ALLOW TO SATISFY
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DISPLAY SHOWS CORRECT DEMAND
IF PREHEAT ACTIVATES THEN ALLOW TO SATISFY
RESISTANCE PUMP AND HARNESS
REMOVE THE PUMP CONNECTOR FROM THE PCB
RESISTANCE HARNESS PUMP
REMOVE THE CONNECTOR FROM THE PUMP ASSEMBLY
REMOVE THE PUMP CONNECTOR FROM THE PCB
FAN RESISTANCE
DISCONNECT THE FAN HARNESS FROM FAN
GAS VALVE RESISTANCE
DISCONNECT LEADS FROM GAS VALVE
DIVERTER VALVE RESISTANCE
DISCONNECT THE DIVERTER VALVE HEAD
HARNESS CONTINUITY PCB TO SPARK GEN
UNPLUG THE CONNECTOR FROM THE PCB
GAS VALVE RESISTANCE
DISCONNECT LEADS FROM GAS VALVE
GAS VALVE RESISTANCE
DISCONNECT LEADS FROM GAS VALVE
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
VOLTAGE AT SPARK GENERATOR
USE INSULATION MAT AS REQUIRED
HARNESS CONTINUITY PCB TO SPARK GEN
UNPLUG THE CONNECTOR FROM THE PCB
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
RESISTANCE GAS VALVE AND HARNESS - BLUE
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
GAS VALVE RESISTANCE - BLUE
DISCONNECT LEADS FROM GAS VALVE
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
VOLTAGE AT SPARK GENERATOR
USE INSULATION MAT AS REQUIRED
HARNESS CONTINUITY PCB TO SPARK GEN
UNPLUG THE CONNECTOR FROM THE PCB
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
RESISTANCE GAS VALVE AND HARNESS - BLUE
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
GAS VALVE RESISTANCE - BLUE
DISCONNECT LEADS FROM GAS VALVE
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
FAN VOLTAGE PERMANENT HALL SENSOR
NO DEMANDS FOR CH OR
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
FLOW REGULATOR/FILTER
WATER OFF
DRAIN OFF EXCESS WATER THROUGH HOT TAP
WHAT FAULT CODE IS SHOWN
THE FAULT CODES ARE
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE GAP
REMOVE FAN AND BURNER FROM TOP OF HEAT EXCHANGER
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
INSULATION PADS
REMOVE FAN AND BURNER
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
OVERHEAT THERMOSTAT RESISTANCE
REMOVE ONE OR BOTH
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
DIVERTER VALVE POSITION (DHW)
REMOVE DIVERTER HEAD
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
OBSERVATION DOES PREHEAT COMPLETE
ENSURE SECONDARY HEA
DIVERTER VALVE POSITION (DHW)
REMOVE DIVERTER HEAD
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
SECONDARY HEAT EXCHANGER
ENSURE SECONDARY HEA
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
DIVERTER VALVE POSITION (CH)
DIVERTER VALVE LOCAT
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DHW INLET VALVE
TURN OFF DHW INLET ISOLATION VALVE
CAN BOILER BE RESET
PRESS THE RESET BUTTON IN THE MIDDLE
OF THE USER DISPLAY
COOL DOWN HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
COOL HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
PUMP RUNS
BOILER MAINS SWITCH
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
DHW HEAT EXCHANGER TEMPERATURE
LOWER PCB
TURN HW STAT TO MAX
CH OPERATION (HEX PROVING)
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
FAN RESISTANCE
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
CAN BOILER BE RESET
PRESS THE RESET BUTTON IN THE MIDDLE
OF THE USER DISPLAY
PUMP RUNS
BOILER MAINS SWITCH
COOL DOWN HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
COOL HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
DHW HEAT EXCHANGER TEMPERATURE
LOWER PCB
TURN HW STAT TO MAX
CH OPERATION (HEX PROVING)
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
COOL HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
PUMP VOLTAGE
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
FUSE F1 PCB
REMOVE FUSE F1 FROM THE CONTROL BOX
RESISTANCE ON OFF SWITCH AND HARNESS
LOWER THE PCB
REM
OBSERVATION PLUG DISPLAY PCB ON TO MAIN PCB - DOES DISPLAY RETURN
DISCONNECT THE HARNE
RESISTANCE HARNESS USER CONTROL
REMOVE HARNESS FROM PCB AND USER CONTROL
VOLTAGE MAIN PCB
DISCONNECT DISPLAY HARNESS FROM THE MAIN PCB
IGNITION ELECTRODE GAP AND CONDITION
REMOVE IGNITION ELECTRODE FROM ITS HOUSING
GAS VALVE OPENS
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
POLARITY
GAIN ACCESS TO MAINS TERMINAL (USE INSULATION MAT AS REQUIRED)
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE HARNESS USER CONTROL
REMOVE HARNESS FROM PCB AND USER CONTROL
INSPECTION DISPLAY PCB CONNECTIONS
REMOVE THE DISPLAY PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
GAS INLET PRESSURE
ENSURE SECONDARY HEA
IGNITION ELECTRODE GAP AND CONDITION
REMOVE IGNITION ELECTRODE FROM ITS HOUSING
GAS VALVE OPENS
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE GAP
REMOVE FAN AND BURNER FROM TOP OF HEAT EXCHANGER
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
DISCONNECT EXTERNAL CONTROLS
DISCONNECT EXTERNAL CONTROLS AND MAKE SAFE
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
DIVERTER VALVE VOLTAGE (DHW)
BOILER MAINS SWITCH ON
REMOVE DIVERTER VALVE CONNECTOR FROM DIVERTER VALVE
DIVERTER VALVE VOLTAGE (PERMANENT)
BOILER MAINS SWITCH ON
DIVERTER VALVE VOLTAGE (DHW)
BOILER MAINS SWITCH ON
REMOVE DIVERTER VALVE CONNECTOR FROM DIVERTER VALVE
DIVERTER VALVE VOLTAGE (PERMANENT)
BOILER MAINS SWITCH ON
OBSERVATION DISCONNECT FAN - DEMAND RECOGNISED?
REMOVE CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
OBSERVATION DISCONNECT FAN HARNESS - DEMAND RECOGNISED?
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
VOLTAGE PERMANENT FAN HALL SENSOR
NO DEMANDS FOR CH OR
VOLTAGE FAN POWER AT PCB
GAIN ACCESS TO BOTTO
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
VOLTAGE FAN AT PCB
DISCONNECT DHW THERM
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
DIVERTER VALVE VOLTAGE (PERMANENT)
BOILER MAINS SWITCH ON
DIVERTER VALVE VOLTAGE (CH)
BOILER MAINS SWITCH ON
CH DEMAND
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
TAPS
ALLOW PRE HEAT TO SATISFY
TEMPERATURE DIFFERENTIAL DHW
TURN HOT WATER TAP ON
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
GAS INLET PRESSURE
ENSURE SECONDARY HEA
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
DIVERTER VALVE POSITION (CH)
DIVERTER VALVE LOCAT
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DIVERTER VALVE VOLTAGE (PERMANENT)
BOILER MAINS SWITCH ON
DIVERTER VALVE VOLTAGE (CH)
BOILER MAINS SWITCH ON
CH DEMAND
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
TAPS
ALLOW PRE HEAT TO SATISFY
POTENTIOMETER RESISTANCE (CH)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
RESISTANCE FAN AND HARNESS
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
RESISTANCE DIVERTER VALVE AND HARNESS
REMOVE DIVERTER VALV
RESISTANCE SPARK GENERATOR AND HARNESS
REMOVE SPARK GENERATOR CONNECTOR FROM THE PCB
OVERHEAT THERMOSTAT RESISTANCE
REMOVE ONE OR BOTH
RESISTANCE GAS VALVE AND HARNESS
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
VOLTAGE GAS VALVE AT PCB
BOILER ON/OFF SWITCH ON
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
OVERHEAT THERMOSTAT RESISTANCE
REMOVE ONE OR BOTH
RESISTANCE GAS VALVE AND HARNESS
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
VOLTAGE GAS VALVE AT PCB
BOILER ON/OFF SWITCH ON
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
RESISTANCE DRY FIRE THERMISTOR AND HARNESS
ENSURE THE BOILER IS COOL
REMOVE THERMISTOR CONNECTOR FROM PCB
VOLTAGE AT SPARK GENERATOR - BLUE
USE INSULATION MAT AS REQUIRED
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
HARNESS CONTINUITY PCB TO SPARK GEN- BLUE
UNPLUG THE CONNECTOR FROM THE PCB
VOLTAGE AT SPARK GENERATOR - BLUE
USE INSULATION MAT AS REQUIRED
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
HARNESS CONTINUITY PCB TO SPARK GEN- BLUE
UNPLUG THE CONNECTOR FROM THE PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
PRESSURE GAS INLET (DHW)
ATTACH U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT
TURN HOT TAP ON
TEMPERATURE DIFFERENTIAL DHW
TURN HOT WATER TAP ON
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
VOLTAGE PERMANENT FAN HALL SENSOR
NO DEMANDS FOR CH OR
VOLTAGE FAN POWER AT PCB
GAIN ACCESS TO BOTTO
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
VOLTAGE FAN AT PCB
DISCONNECT DHW THERM
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
OVERHEAT THERMOSTAT RESISTANCE
REMOVE ONE OR BOTH
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
BURNER IGNITES LF
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
RESISTANCE CONTROL THERMISTOR FLOW AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTOR RETURN AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
REMOVE PLUG FROM PCB
GAS INLET PRESSURE
ENSURE SECONDARY HEA
System Information