Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Remove flame detection electrode from its housing
Unplug connection from PCB

Measurement:

Test 1:
Carry out a continuity check of the earth lead between the PCB connector and the fan earth tab.
Expect zero resistance.
Test 2:
Carry out a continuity check of the flame sense lead between the PCB connector and detection electrode connection.
Expect zero resistance.
Test 3:
Thoroughly inspect the condition of the earth and rectification leads, looking for damaged insulation, evidence of the lead being trapped or heat damaged and excessively tight bends or kinks.