Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Attach a temperature clamp to the flow pipe directly underneath the overheat thermostat coil and use a temperature probe to monitor the temperature of the nut above the pump
DHW temperature set to MAX
Selector Switch in Hot Water Position
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the burner to ignite and boiler to run for at least 2 minutes.
Monitor the temperature differential between the flow and return.
Differential should be approximately 20°C or less.