Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect the leads from the air pressure switch
Remove connector CN1 from the PCB
Remove connector CN1 from the PCB
Measurement:
Using the air pressure switch testing kit, increase the pressure on the air pressure switch until short circuit can be measured across the common and normally open terminals of the switch.
With the testing kit still connected, reconnect the wires to the air pressure switch.
Measure resistance across the DHW cut-off
circuit (yellow and black wires on CN1).
Expected resistance short circuit (zero Ohms).
With the testing kit still connected, reconnect the wires to the air pressure switch.
Measure resistance across the DHW cut-off
circuit (yellow and black wires on CN1).
Expected resistance short circuit (zero Ohms).

Isolate as per TOPs P4
and refit as necessary