Set Appliance State:
Mains Power Off
Ensure primary heat exchanger is below 40°C (to ensure a demand for preheat)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
If required reset appliance (press and hold reset button for 5 seconds, then release).
Turn ECO mode OFF (press and hold the ECO button until it is no longer illuminated).
This turns the pre heat function ON.
Does the pump run with a preheat demand?
Notes:
1. Do not take sound or vibration as a sign of the pump running.
2. Once test is complete remember to turn ECO mode back on (button illuminated).
Turn ECO mode OFF (press and hold the ECO button until it is no longer illuminated).
This turns the pre heat function ON.
Does the pump run with a preheat demand?
Notes:
1. Do not take sound or vibration as a sign of the pump running.
2. Once test is complete remember to turn ECO mode back on (button illuminated).