Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove red wires from primary sensor
Ensure primary heat exchanger is below 60° C
Carefully remove sensor.
Ensure primary heat exchanger is below 60° C
Carefully remove sensor.
Measurement:
Measure resistance across the exposed sensor terminals.
The resistance should conform to the table below:
Refit sensor after test
The resistance should conform to the table below:
| Temperature °C | Resistance in kOhms | 20 - 30 | 8.0 - 16.0 |
| 30 - 40 | 6.0 - 10.0 |
| 40 - 50 | 3.9 - 8.0 |
| 50 - 60 | 2.5 - 5.5 |
| 60 - 70 | 1.5 - 3.0 |
Refit sensor after test

Isolate as per TOPs P4
and refit as necessary