Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach pressure gauge to inlet pressure test point on gas valve
Unclip Diverter Valve head from the body and leave
in a safe position
Unclip Diverter Valve head from the body and leave
in a safe position
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Reset appliance if necessary
(press and hold reset button for 5 seconds, then release).
Operate boiler at maximum output. CLICK HERE FOR INSTRUCTIONS
Does the pressure gauge show a constant inlet gas
pressure above 16.5mbar (28mbar for LPG appliances)?
Note: When U-gauge is removed test point should be tightened & checked for gas soundness.
(press and hold reset button for 5 seconds, then release).
Operate boiler at maximum output. CLICK HERE FOR INSTRUCTIONS
Does the pressure gauge show a constant inlet gas
pressure above 16.5mbar (28mbar for LPG appliances)?
Note: When U-gauge is removed test point should be tightened & checked for gas soundness.
Isolate as per TOPs P4
and refit as necessary