Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect flame sense lead (green lead) from
sense electrode and secure it as shown
sense electrode and secure it as shown
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Measure voltage across the disconnected flame sense lead and a suitable earth point.
Expected voltage approximately 50 VAC
Expected voltage approximately 50 VAC

Isolate as per TOPs P4
and refit as necessary