Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Remove connector (blue wires) from modulating solenoid
Set service potentiometer to MAX
Remove connector (blue wires) from modulating solenoid
Set service potentiometer to MAX
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Appliance On/Off control set to ON position.
Reset lockout as necessary.
Allow ignition sequence to commence.
After approximately 10 seconds measure voltage at disconnected connector.
Expect approximately 20 vdc or greater.
Reset lockout as necessary.
Allow ignition sequence to commence.
After approximately 10 seconds measure voltage at disconnected connector.
Expect approximately 20 vdc or greater.

Isolate as per TOPs P4
and refit as necessary