Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Attach temperature probes as indicated by the red arrows
DHW thermostat to MAX
DHW flow rate of 8.0 l/min approximately
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the burner to ignite and appliance to run for at least 2 minutes.
With the appliance still running measure the temperature differential across the plate heat exchanger.
Expect a differential of approximately 34°C or less.