Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
CH temperature selector set at MAX
Attach U-gauge to gas valve outlet pressure test point
Heating system should be cold
Boiler ON/OFF switch ON
Attach U-gauge to gas valve outlet pressure test point
Heating system should be cold
Boiler ON/OFF switch ON
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow boiler to commence its ignition sequence and the burner to ignite.
Burner should run at 0.7mb for 2 mins then ramp up over 1 min to its set pressure.
Does boiler operate as above and is the CH burner pressure
set to an appropriate level for the size of the system?
Notes:
1. The boiler is fully modulating and pressure ramp up will only take place if the
system is cold and does not reach a satisfactory temperature in the initial 2 minutes.
2. If system temperature rise is satisfactory no increase in burner pressure
should be considered normal operation.
3. When U-gauge is removed pressure test point should be tightened & checked for gas tightness.
Burner should run at 0.7mb for 2 mins then ramp up over 1 min to its set pressure.
Does boiler operate as above and is the CH burner pressure
set to an appropriate level for the size of the system?
Notes:
1. The boiler is fully modulating and pressure ramp up will only take place if the
system is cold and does not reach a satisfactory temperature in the initial 2 minutes.
2. If system temperature rise is satisfactory no increase in burner pressure
should be considered normal operation.
3. When U-gauge is removed pressure test point should be tightened & checked for gas tightness.
Isolate as per TOPs P4
and refit as necessary