Set Appliance State:

Gas Off
Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance

Measurement:

Measure resistance across the exposed terminals of the sensor.
Note: Resistance measured will vary according to the boiler temperature the cooler the boiler the higher the resistance. The resistance should conform to the table below.
Temperature °CResistance in kOhms
10-2020.0-12.5
20-3012.5-8.0
30-408.0-5.2
40-505.2-3.5
50-603.5-2.4
60-702.5-1.7
70-801.7-1.2
Reconnect leads after test.