Set Appliance State:
Mains Power Off
CH Demand
Selector switch to CH - MAX position
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow boiler to fire and heat system to above 70 degrees C,
(maximum temperature on selector is approximately 82 degrees C).
Remove CH demand.
Does pump and fan overrun to dissipate heat?
Pump should run until system temperature falls to below 60 degrees C. Fan should overrun for approx. 4 minutes.
Note:
It may be necessary to reduce heating load by turning off some radiators to reduce time taken for this test.
Isolate as per TOPs P4
and refit as necessary