Set Appliance State:

Set Multimeter to Resistance Set meter to measure resistance
Isolate Mains Power to appliance as per TOPs P4
Remove brown and yellow wires from CH sensor

Measurement:

Measure resistance between the terminals on the sensor.
The resistances measured will depend upon the boiler temperature, the table shows some typical measurements.
The working range is between 1.5-25kOhms.
Temperature °CResistance in kOhms
15-2015.0-9.0
20-509.0-3.0
50-603.0-2.0
60-852.0-1.5