Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
This test is only valid if the ambient air temperature around the frost stat is greater than 8 deg C
Operating switch in Off position
Gain access to PCB (use insulation mat as required)
Disconnect the wires to the frost thermostat, connected to 4 and 5 on connector X4 at the PCB, and make safe
Ensure no demands
This test is only valid if the ambient air temperature around the frost stat is greater than 8 deg C
Operating switch in Off position
Gain access to PCB (use insulation mat as required)
Disconnect the wires to the frost thermostat, connected to 4 and 5 on connector X4 at the PCB, and make safe
Ensure no demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Does the demand neon still illuminate with no demand?

Isolate as per TOPs P4
and refit as necessary