Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Disconnect Red wires from connections 7 & 8 on the upper connector block
(Ensure other end of disconnected wires are connected to the DHW sensor)
Ensure DHW is cool
Disconnect Red wires from connections 7 & 8 on the upper connector block
(Ensure other end of disconnected wires are connected to the DHW sensor)
Ensure DHW is cool
Measurement:
Measure resistance between the two Red wires.
Note:
Resistance measured will vary according to the boiler temperature, the cooler the boiler the higher the resistance.
The resistance should conform to the table below.
Note:
Resistance measured will vary according to the boiler temperature, the cooler the boiler the higher the resistance.
The resistance should conform to the table below.
| Temperature °C | Resistance in kOhms |
| 10-20 | 19.9-12.4 |
| 20-30 | 12.4-7.9 |
| 30-40 | 7.9-5.2 |
| 40-50 | 5.2-3.5 |
| 50-60 | 3.5-2.4 |
| 60-70 | 2.4-1.7 |
| 70-80 | 1.7-1.2 |

Isolate as per TOPs P4
and refit as necessary