REMEHA AVANTA EXCLUSIVE 39C
GLOBALLY REPLACED
OBSERVATION BOILER SELF CHECK
ENSURE APPLIANCE IS COOL
NO DEMANDS FOR DHW OR CH
FUSE INVESTIGATION TREE
OUTSIDE MODEL
E0 - FLOW OR RETURN SENSOR FAULT
OUTSIDE MODEL
E1 - FLOW TEMP HIGHER THAN MAX TEMP
OUTSIDE MODEL
E2 - RETURN TEMP HIGHER THAN FLOW
OUTSIDE MODEL
E3 - CONTROL UNIT OR EARTH FAULT
OUTSIDE MODEL
E4 - MORE THAN 4 ATTEMPTS WITHOUT FLAME FORMATION
OUTSIDE MODEL
E5 - NO IONISATION OR MORE THAN 5 IONISATION FAILURES
OUTSIDE MODEL
E6 - UNWANTED FLAME FORMATION
OUTSIDE MODEL
E7 - NO WATER OR PUMP NOT WORKING
OUTSIDE MODEL
E8 - FAN FAULT
OUTSIDE MODEL
E9 - NO WATER OR PUMP NOT WORKING
OUTSIDE MODEL
E10 - NO THROUGH FLOW DURING VENTING CYCLE
OUTSIDE MODEL
E11 - AIR BOX TEMPERATURE TOO HIGH
OUTSIDE MODEL
E13 - HEAT EXCHANGER FUSE BLOWN
OUTSIDE MODEL
E43 - PARAMETER LIMITS
OUTSIDE MODEL
E44 - PARAMETER CHECK
OUTSIDE MODEL
E45 - DEFAULT PARAMETERS
OUTSIDE MODEL
OBSERVATION BOILER REACTS TO CH DEMAND
BOILER IN STANDBY ('0' ON DISPLAY)
OBSERVATION BOILER REACTS TO DHW DEMAND
BOILER IN STANDBY ('0' ON DISPLAY)
OBSERVATION PREHEAT
ENSURE APPLIANCE IS COOL AND THERE IS NO DEMAND FOR DHW OR CH
COMBUSTION TEST
ATTACH FGA TO COMBUSTION TEST POINT
OVERHEAT TREE
OUTSIDE MODEL
INFORMATION PREVIOUS FAULT CODES
Z REDIRECT
E13 -2
Z REDIRECT
E2 - STUCK IN FAULT
PCB - CONTROL
OPERATION CH - TEMPERATURE LOW (RETURN)
SENSOR - TEMPERATURE
OBSERVATION PREHEAT - KETTLES
FILTER SYSTEM - PRIMARY FLOW
OPERATION DHW - DHW RUNS HOT COLD - FLOW
SENSOR - TEMPERATURE
OPERATION DHW - DHW RUNS HOT COLD - RETURN
SENSOR - TEMPERATURE
E0 - RETURN
SET - CABLE
OBSERVATION DISPLAY ILLUMINATESFAULT CODES
Z REDIRECT
OBSERVATION PREHEAT - KETTLES
PLATE HEAT EXCHANGER
OVERHEAT INVESTIGATION - FLOW
SENSOR - TEMPERATURE
OVERHEAT INVESTIGATION - RETURN
SENSOR - TEMPERATURE
OVERHEAT INVESTIGATION
SENSOR FITMENT / WIRING
OVERHEAT INVESTIGATION - NO POWER TO PUMP
PCB - CONTROL
OVERHEAT INVESTIGATION - INSPECTIONS
FILTER SYSTEM - PRIMARY FLOW
OVERHEAT INVESTIGATION - INSPECTIONS
PLATE HEAT EXCHANGER
ADDITIONAL TEST FLOW SWITCH
FLOW SWITCH ASSEMBLY
INFORMATION SET FLOW TEMPERATURE
Z REDIRECT
INFORMATION SET DHW TEMPERATURE
Z REDIRECT
INFORMATION DISABLE PREHEAT
Z REDIRECT
INTERMITTENT IGNITION
INLET PRESSURE
INFORMATION STATUS CODES
Z REDIRECT
OPERATION PREHEAT - TEMPERATURE LOW
PCB SETTINGS
OPERATION DHW - DHW RUNS HOT COLD
FILTER SYSTEM - PRIMARY FLOW
OVERHEAT INVESTIGATION - DIFFERENTIALS
FILTER SYSTEM - PRIMARY FLOW
OPERATION PREHEAT (WIRED VIA X13)
SET - CABLE
OPERATION PREHEAT (WIRED VIA X13)
PCB - CONTROL
OPERATION PREHEAT (WIRED VIA X9)
SET - CABLE
OPERATION PREHEAT - (WIRED VIA X9)
PCB - CONTROL
OPERATION PREHEAT (NO WPS)
PCB - CONTROL
OBSERVATION PREHEAT
EXTERNAL CONTROLS / INTERNAL TIMER
E10 - RUNNING SLOW
PUMP
E10
FILTER SYSTEM - PRIMARY FLOW
E10
PLATE HEAT EXCHANGER
OBSERVATION PREHEAT
FLOW SWITCH ASSEMBLY
OBSERVATION PREHEAT - FLOW SWITCH STUCK ON
SET - CABLE
OPERATION DHW - DHW COOL RADS COOL
FILTER SYSTEM - PRIMARY FLOW
OPERATION DHW - DHW COOL RADS COOL
INLET PRESSURE
OPERATION DHW - DHW COOL RADS COOL
HEAT EXCHANGER
OPERATION DHW - DHW COOL RADS COOL
BURNER / GASKET
OBSERVATION DISPLAY ILLUMINATES - HARNESS
PCB - DISPLAY PRINT
E8 - NO VOLTAGE TO FAN
PCB - CONTROL
NO DEMAND TO FAN
PCB - CONTROL
E8 - 24V FAN
SET - CABLE
COMBUSTION TEST INTERMITTENT IGNITION
SIPHON ASSEMBLY C/W HOSE
COMBUSTION TEST INTERMITTENT IGNITION
INLET PRESSURE
COMBUSTION TEST INTERMITTENT IGNITION
HEAT EXCHANGER
COMBUSTION TEST INTERMITTENT IGNITION
BURNER / GASKET
COMBUSTION TEST INTERMITTENT IGNITION
SILENCER - AIR SUPPLY
E4 DUMMY - GO TO DOES BURNER IGNITE PAGE
Z REDIRECT
INFORMATION CASE REMOVAL
Z REDIRECT
E5 DUMMY - GO TO DOES BURNER IGNITE PAGE
Z REDIRECT
E0 - FLOW
SENSOR - TEMPERATURE
E0
PCB - CONTROL
E1 - FLOW
SENSOR - TEMPERATURE
E1 - STUCK IN FAULT
PCB - CONTROL
E2
SENSOR FITMENT / WIRING
E2 - RETURN
SENSOR - TEMPERATURE
E2 - FLOW
SENSOR - TEMPERATURE
E3
PCB - CONTROL
E6
PCB - CONTROL
E13 - NO EXTRA SENSOR
SET - CABLE
E13
KIT - SERVICE
E7 DUMMY - N/A TO APPLIANCE? GO TO E10
Z REDIRECT
E13 - EXTRA SENSOR
SET - CABLE
E13 - STUCK IN FAULT
PCB - CONTROL
E9 (WIRED VIA X9)
SET - CABLE
E9 (WIRED VIA X13)
SET - CABLE
E9 (WIRED VIA X13)
PCB - CONTROL
E9 - (WIRED VIA X9)
PCB - CONTROL
E9 (NO WPS)
PCB - CONTROL
E10 (FLOW)
SENSOR - TEMPERATURE
E10 (RETURN)
SENSOR - TEMPERATURE
E11 DUMMY - N/A TO APPLIANCE? GO TO E6
Z REDIRECT
OPERATION PREHEAT - TEMPERATURE LOW (FLOW)
SENSOR - TEMPERATURE
OPERATION PREHEAT - TEMPERATURE LOW (RETURN)
SENSOR - TEMPERATURE
E44 DUMMY - GO TO E43
Z REDIRECT
E45 DUMMY - GO TO E6
Z REDIRECT
E8 - 240V FAN (24V)
SET - CABLE
OBSERVATION BOILER REACTS TO CH DEMAND - IGNORING DEMAND
PCB - CONTROL
OBSERVATION BOILER REACTS TO DHW DEMAND
SET - CABLE
OBSERVATION BOILER REACTS TO DHW DEMAND
SENSOR - FLOW - DHW
OBSERVATION BOILER REACTS TO DHW DEMAND
EXTERNAL CONTROLS / INTERNAL TIMER
OBSERVATION PUMP OVERRUN
PCB - CONTROL
E10
SENSOR FITMENT / WIRING
E43
PCB SETTINGS
E8 - 240V FAN (240V)
SET - CABLE
FUSE INVESTIGATION
PUMP
FUSE INVESTIGATION
BLOCK - GAS CONSUMPTION
FUSE INVESTIGATION
IGNITION - TRANSFORMER
FUSE INVESTIGATION
ACTUATOR - THREE WAY VALVE
OPERATION CH
VESSEL - EXPANSION
OPERATION CH - TEMPERATURE LOW (FLOW)
SENSOR - TEMPERATURE
OPERATION CH - TEMPERATURE LOW
PCB SETTINGS
FAULT CODES
Z REDIRECT
OPERATION CH - RADS NOT HEATING
VALVE 22MM - FLOW & RETURN
OPERATION DHW - TOO HOT (FLOW)
SENSOR - TEMPERATURE
OPERATION DHW - TOO HOT
PCB SETTINGS
OPERATION DHW - DHW COOL RADS WARM
PCB - CONTROL
OPERATION DHW - DHW COOL RADS WARM
SET - CABLE
BURNER DOES NOT IGNITE SPARKING HEARD
SIPHON ASSEMBLY C/W HOSE
BURNER DOES NOT IGNITE SPARKING HEARD - RESISTANCE
BLOCK - GAS CONSUMPTION
BURNER DOES NOT IGNITE SPARKING HEARD
HEAT EXCHANGER
BURNER DOES NOT IGNITE SPARKING HEARD
BURNER / GASKET
BURNER DOES NOT IGNITE SPARKING PRESENT
PCB - CONTROL
BURNER DOES NOT IGNITE SPARKING HEARD
SILENCER - AIR SUPPLY
BURNER IGNITES NOISLY OR BAFFLES
SIPHON ASSEMBLY C/W HOSE
BURNER IGNITES NOISLY OR BAFFLES
INLET PRESSURE
BURNER IGNITES NOISLY OR BAFFLES
HEAT EXCHANGER
BURNER IGNITES NOISLY OR BAFFLES
BURNER / GASKET
BURNER IGNITES NOISLY OR BAFFLES
SILENCER - AIR SUPPLY
BURNER IGNITES NOISLY OR BAFFLES
VENTURI
BURNER DOES NOT ESTABLISH
SIPHON ASSEMBLY C/W HOSE
BURNER DOES NOT ESTABLISH
PCB - CONTROL
BURNER DOES NOT ESTABLISH
INLET PRESSURE
BURNER DOES NOT ESTABLISH - SPARK GENERATOR
SET - CABLE
BURNER DOES NOT ESTABLISH
HEAT EXCHANGER
BURNER DOES NOT ESTABLISH
ELECTRODE - IGNITION / IONISATION C/W LEAD
BURNER DOES NOT ESTABLISH
BURNER / GASKET
BURNER DOES NOT ESTABLISH
SILENCER - AIR SUPPLY
BURNER DOES NOT ESTABLISH
VENTURI
FUSE INVESTIGATION
FAN ASSEMBLY
FUSE INVESTIGATION
INNER ASSEMBLY - THREE WAY VALVE
INTERMITTENT IGNITION
SIPHON ASSEMBLY C/W HOSE
INTERMITTENT IGNITION RECTIFICATION VOLTAGE
PCB - CONTROL
INTERMITTENT IGNITION - SPARK GENERATOR DAMAGED
SET - CABLE
INTERMITTENT IGNITION
HEAT EXCHANGER
INTERMITTENT IGNITION
ELECTRODE - IGNITION / IONISATION C/W LEAD
INTERMITTENT IGNITION
BURNER / GASKET
INTERMITTENT IGNITION
SILENCER - AIR SUPPLY
INTERMITTENT IGNITION
VENTURI
INTERMITTENT IGNITION - RESISTANCE
BLOCK - GAS CONSUMPTION
BURNER DOES NOT IGNITE NO SPARKING
PCB - CONTROL
INTERMITTENT IGNITION NO SPARKING
PCB - CONTROL
INTERMITTENT IGNITION - SPARK GENERATOR O/C
SET - CABLE
E10 - NO POWER TO PUMP
PCB - CONTROL
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
OPERATION CH - RADS NOT HEATING - NO VOLTAGE TO DIVERTER
PCB - CONTROL
OPERATION CH - RADS NOT HEATING - DIVERTER
SET - CABLE
OPERATION CH - RADS NOT HEATING
INNER ASSEMBLY - THREE WAY VALVE
OBSERVATION DISPLAY ILLUMINATES
FUSE MAINS
OBSERVATION DISPLAY ILLUMINATES
FUSE 2A GLASS
OBSERVATION DISPLAY ILLUMINATES
PCB - CONTROL
OBSERVATION DISPLAY ILLUMINATES - NO SELF CHECK
PCB - CONTROL
INFORMATION PARAMETER ACCESS
Z REDIRECT
DHW COOL RADS COOL
EXTERNAL MIXING
OPERATION DHW - DHW COOL RADS COOL - FLOW
SENSOR - TEMPERATURE
OPERATION DHW - DHW COOL RADS COOL - RETURN
SENSOR - TEMPERATURE
OPERATION DHW - DHW COOL RADS COOL
SIPHON ASSEMBLY C/W HOSE
COMBUSTION TEST
SIPHON ASSEMBLY C/W HOSE
COMBUSTION TEST
FLUE
COMBUSTION TEST
INLET PRESSURE
COMBUSTION TEST
HEAT EXCHANGER
COMBUSTION TEST
BURNER / GASKET
COMBUSTION TEST
SILENCER - AIR SUPPLY
COMBUSTION TEST
VENTURI
OBSERVATION PREHEAT - DHW COOL RADS WARM
PCB - CONTROL
OBSERVATION PREHEAT - DHW COOL RADS WARM
SET - CABLE
OBSERVATION DHW FLOW RATE
WATER SUPPLY
OBSERVATION PREHEAT - ON NO DEMAND
EXTERNAL CONTROLS / INTERNAL TIMER
OBSERVATION DHW FLOW RATE
VALVE 15MM - MAIN COLD WATER
OBSERVATION DHW FLOW RATE
FLOW SWITCH ASSEMBLY
E13 - 1
Z REDIRECT
E2
Z REDIRECT
OPERATION CH - TEMPERATURE LOW
PCB - CONTROL
OBSERVATION PREHEAT - KETTLES
SYSTEM PRESSURE
OBSERVATION PREHEAT - KETTLES
PRESSURE GAUGE
OPERATION DHW - RUNS HOT COLD
SYSTEM PRESSURE
OPERATION DHW - DHW RUNS HOT COLD
PRESSURE GAUGE
OPERATION DHW - DHW RUNS HOT COLD
PCB - CONTROL
OPERATION DHW - DHW RUNS HOT COLD
HEAT EXCHANGER (WATERWAYS)
E0 - RETURN
SENSOR - TEMPERATURE
OBSERVATION DISPLAY ILLUMINATESFAULT CODES 2
Z REDIRECT
OBSERVATION PREHEAT - KETTLES
HEAT EXCHANGER (WATERWAYS)
OVERHEAT INVESTIGATION
PRESSURE GAUGE
OVERHEAT INVESTIGATION
SYSTEM PRESSURE
OVERHEAT INVESTIGATION - INSPECTIONS
HEAT EXCHANGER (WATERWAYS)
OVERHEAT INVESTIGATION - DIFFERENTIALS
HEAT EXCHANGER (WATERWAYS)
OVERHEAT INVESTIGATION - DIFFERENTIALS
NO FAULT OVERHEAT
ADDITIONAL TEST FLOW SWITCH
SENSOR - FLOW - DHW
OBSERVATION DISPLAY ILLUMINATES
PCB - DISPLAY PRINT
OPERATION DHW - DHW RUNS HOT COLD
PLATE HEAT EXCHANGER
OVERHEAT INVESTIGATION - DIFFERENTIALS
PLATE HEAT EXCHANGER
OPERATION PREHEAT
SYSTEM PRESSURE
OPERATION PREHEAT
PRESSURE GAUGE
OPERATION PREHEAT (WIRED VIA X13)
PRESSURE SWITCH
OPERATION PREHEAT (WIRED VIA X13)
RESET AFTER E9
OPERATION PREHEAT (WIRED VIA X9)
PRESSURE SWITCH
OPERATION PREHEAT (WIRED VIA X9)
RESET AFTER E9
OPERATION PREHEAT (NO WPS)
RESET AFTER E9
OBSERVATION PREHEAT - NOT FIRING
PCB - CONTROL
OBSERVATION PREHEAT - IGNORING DEMAND
PCB - CONTROL
E10
HEAT EXCHANGER (WATERWAYS)
OBSERVATION PREHEAT
OPEN TAP OR WATER LEAK
OBSERVATION PREHEAT
SENSOR - FLOW - DHW
OPERATION DHW - DHW COOL RADS COOL
HEAT EXCHANGER (WATERWAYS)
OPERATION DHW - DHW COOL RADS COOL
PLATE HEAT EXCHANGER
OPERATION DHW - DHW COOL RADS COOL
PCB - CONTROL
OPERATION DHW - DHW COOL RADS COOL GAS RATE LOW
PCB - CONTROL
OBSERVATION DISPLAY ILLUMINATES - SELF CHECK STARTS
PCB - CONTROL
NO FAULT INTERMITTENT IGNITION
NO FAULT INTERMITTENT IGNITION
E8
FAN ASSEMBLY
COMBUSTION TEST INTERMITTENT IGNITION
BLOCK - GAS CONSUMPTION
E0 - FLOW
SET - CABLE
E0
Z REDIRECT
E1
Z REDIRECT
E3
Z REDIRECT
E6
Z REDIRECT
E13 - NO EXTRA SENSOR
HEAT EXCHANGER (FUSE)
E13 - EXTRA SENSOR
HEAT EXCHANGER (FUSE)
E9
SYSTEM PRESSURE
E9 (WIRED VIA X9)
PRESSURE SWITCH
E9 (WIRED VIA X13)
PRESSURE SWITCH
E9 (WIRED VIA X9)
RESET AFTER E9
E9 (NO WPS)
RESET AFTER E9
E10
SYSTEM PRESSURE
E10
PRESSURE GAUGE
E9 (WIRED VIA X13)
RESET AFTER E9
OPERATION PREHEAT - TEMPERATURE LOW
PCB - CONTROL
E8
FAN (240V) + PCB
OBSERVATION BOILER REACTS TO CH DEMAND
EXTERNAL CONTROLS / INTERNAL TIMER
OBSERVATION BOILER REACTS TO CH DEMAND
LOW VOLTAGE CONTROLS
OBSERVATION BOILER REACTS TO DHW DEMAND
FLOW SWITCH ASSEMBLY
E43
PCB - CONTROL
FUSE INVESTIGATION - GAS VALVE
SET - CABLE
FUSE INVESTIGATION
PCB - CONTROL (FUSE INVESTIGATION)
FUSE INVESTIGATION - SPARK GENERATOR
SET - CABLE
FUSE INVESTIGATION - DIVERTER VALVE
SET - CABLE
OPERATION CH
PIPE - PUMP TO EXPANSION VESSEL
FAULT CODES 2
Z REDIRECT
OPERATION DHW - TOO HOT
PCB - CONTROL
OPERATION DHW - DHW COOL RADS WARM
INNER ASSEMBLY - THREE WAY VALVE
OPERATION DHW - DHW COOL RADS WARM
ACTUATOR - THREE WAY VALVE
BURNER DOES NOT IGNITE NO SPARKING
ELECTRODE - IGNITION / IONISATION C/W LEAD
BURNER DOES NOT IGNITE SPARKING HEARD
FAN ASSEMBLY
BURNER DOES NOT IGNITE SPARKING HEARD
INLET PRESSURE
BURNER DOES NOT IGNITE SPARKING HEARD - NOT OPENING
BLOCK - GAS CONSUMPTION
BURNER DOES NOT IGNITE SPARKING HEARD - NOT OPENING FULLY
BLOCK - GAS CONSUMPTION
BURNER IGNITES NOISLY OR BAFFLES
BLOCK - GAS CONSUMPTION
BURNER DOES NOT ESTABLISH
IGNITION - TRANSFORMER
FUSE INVESTIGATION - FAN
SET - CABLE
INTERMITTENT IGNITION - GAS VALVE
SET - CABLE
OBSERVATION PREHEAT - DHW COOL RADS WARM
INNER ASSEMBLY - THREE WAY VALVE
BURNER DOES NOT IGNITE NO SPARKING
IGNITION - TRANSFORMER
INTERMITTENT IGNITION NO SPARKING
IGNITION - TRANSFORMER
E10 - NOT RUNNING
PUMP
OPERATION CH - RADS NOT HEATING
ACTUATOR - THREE WAY VALVE
FUSE INVESTIGATION - MAINS
Z REDIRECT
FUSE INVESTIGATION - PCB FUSE
Z REDIRECT
OBSERVATION DISPLAY ILLUMINATES
FAN ASSEMBLY
OBSERVATION DISPLAY ILLUMINATES - NO DISPLAY
FAN ASSEMBLY
E9
PRESSURE GAUGE
OPERATION DHW - DHW COOL RADS COOL
PRESSURE GAUGE
OPERATION DHW - DHW COOL RADS COOL
SYSTEM PRESSURE
COMBUSTION TEST
BLOCK - GAS CONSUMPTION
OBSERVATION PREHEAT - DHW COOL RADS WARM
ACTUATOR - THREE WAY VALVE
OPERATION PREHEAT - RADS HEAT - STUCK ON CH
PCB - CONTROL
OBSERVATION DHW FLOW RATE
PLATE HEAT EXCHANGER
BOILER KETTLING OR NOISY
CHARACTERISTIC TEST FROM OBSERVATION PREHEAT
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
BOILER SHOWS FAULT CODE
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
BOILER DOES NOT REFIRE FOR PREHEAT
CHARACTERISTIC TEST FROM OBSERVATION PREHEAT
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
WATER PRESSURE SWITCH WIRED VIA X9
CHARACTERISTIC TEST FROM OBSERVATION WATER PRESSURE SWITCH
WATER PRESSURE SWITCH WIRED VIA X13
CHARACTERISTIC TEST FROM OBSERVATION WATER PRESSURE SWITCH
BOILER COMPLETES PREHEAT AS ABOVE BUT FAN CONTINUES TO RUN
CHARACTERISTIC TEST FROM OBSERVATION PREHEAT
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
WATER PRESSURE SWITCH WIRED VIA X9
CHARACTERISTIC TEST FROM OBSERVATION WATER PRESSURE SWITCH
WATER PRESSURE SWITCH WIRED VIA X13
CHARACTERISTIC TEST FROM OBSERVATION WATER PRESSURE SWITCH
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
PREHEAT RUNS BUT SHUTS DOWN AT INCORRECT TEMPERATURE
CHARACTERISTIC TEST FROM OBSERVATION PREHEAT
PREHEAT UNABLE TO COMPLETE BECAUSE RADS BEGIN TO HEAT
CHARACTERISTIC TEST FROM OBSERVATION PREHEAT
BOILER SHOWS FAULT CODE OTHER THAN E4 / E5 AT ANY POINT DURING SELF CHECK
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
BOILER REACHES TEMPERATURE BUT RADIATORS NOT HEATING PROPERLY
CHARACTERISTIC TEST FROM OPERATION CH
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
BOILER AND RADIATOR TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW COOL, RADS BEGIN TO HEAT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT COLD
CHARACTERISTIC TEST FROM OPERATION DHW
DHW COOL, RADIATORS REMAIN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
NO IGNITION / POOR OR INTERMITTENT IGNITION / FAULT CODE E4 OR E5 SHOWN
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
BURNER DOES NOT IGNITE, NO SPARKING HEARD
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER DOES NOT IGNITE, SPARKING HEARD
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
INLET PRESSURE DROPS BELOW 18MB (NG) OR 37MB (LPG)
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
INLET PRESSURE DOES NOT DROP DURING SPARKING
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
BURNER IGNITES NOISILY OR BAFFLES OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
DISPLAY IS BLANK
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
DISPLAY FLASHES F ONLY
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY ILLUMINATES
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
PRESSURE OK ON GAUGE BUT DOES NOT INCREASE WHEN WATER ADDED
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
WATER PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION SYSTEM PRESSURE
DIVERTER VALVE DOES NOT MOVE DURING SELF CHECK
CHARACTERISTIC TEST FROM OBSERVATION DIVERTER VALVE MOVEMENT DHW
DIVERTER VALVE DOES NOT FINISH IN EXTENDED POSITION
CHARACTERISTIC TEST FROM OBSERVATION DIVERTER VALVE MOVEMENT DHW
02/12/2019 12:24:38 1911_1_50_1 06/01/2020 14:29:30
11/12/2019 11:19:13
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR FLOW
DISCONNECT PLUG FROM FLOW SENSOR
VOLTAGE PUMP AT PCB
{GAINPCBACS}
DISCONNECT PLUG FROM FLOW THERMISTOR
INSPECTION FLOW SWITCH ASSEMBLY
ISOLATE MAINS WATER
RESISTANCE HARNESS WATER PRESSURE SWITCH (X13)
DISCONNECT PLUG FROM FLOW SWITCH
DISCONNECT X13 FROM THE PCB
RESISTANCE HARNESS WATER PRESSURE SWITCH (X9)
DISCONNECT PLUG FROM FLOW SWITCH
DISCONNECT X9 FROM THE PCB
VOLTAGE FLOW SWITCH TO PCB (FLOW SWITCH OFF)
REMOVE FLOW SWITCH FROM APPLIANCE BUT LEAVE CONNECTED ELECTRICALLY
RESISTANCE HARNESS FLOW SWITCH
DISCONNECT PLUG FROM FLOW SWITCH
DISCONNECT X13 FROM THE PCB
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET TEST POINT
RESISTANCE HARNESS DISPLAY PCB
REMOVE DISPLAY PCB HARNESS FROM APPLIANCE
SOCKET AND SEE TEST
{GAINPCBACS}
RESISTANCE SENSOR FLOW
DISCONNECT PLUG FROM FLOW SENSOR
RESISTANCE HARNESS RETURN SENSOR
DISCONNECT PLUG FROM RETURN SENSOR
DISCONNECT X13 FROM THE PCB
RESISTANCE HARNESS HEAT EXCHANGER FUSE
{GAINPCBACS}
DISC
OBSERVATION 24V OR 240V FAN
{GAINPCBACS}
RESISTANCE HARNESS WATER PRESSURE SWITCH (X9)
DISCONNECT PLUG FROM FLOW SWITCH
DISCONNECT X9 FROM THE PCB
RESISTANCE HARNESS WATER PRESSURE SWITCH (X13)
DISCONNECT PLUG FROM FLOW SWITCH
DISCONNECT X13 FROM THE PCB
RESISTANCE HEAT EXCHANGER FUSE AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE HARNESS FAN (240V)
DISCONNECT HIGH VOLTAGE PLUG FROM FAN
DISCONNECT CONNECTOR X3 FROM THE PCB
VOLTAGE EXTERNAL CONTROLS CH INTO BOILER
{GAINPCBACS}
RESISTANCE FAN
DISCONNECT PLUG FROM FAN
RESISTANCE GAS VALVE (FUSE INV)
DISCONNECT PLUG FROM GAS VALVE
(LOOSEN SCREW HOLDING SPARK GENERATOR)
RESISTANCE SPARK GENERATOR
REMOVE SPARK GENERATOR FROM APPLIANCE
RESISTANCE DIVERTER VALVE
UNCLIP AND DISCONNEC
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
(LOOSEN SCREW HOLDING SPARK GENERATOR)
RESISTANCE PUMP AND HARNESS
{GAINPCBACS}
DISCONNECT X4 FROM THE PCB
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
(LOOSEN SCREW HOLDING SPARK GENERATOR)
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
DISC
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
DISC
VOLTAGE PUMP AT PCB
{GAINPCBACS}
DISCONNECT PLUG FROM FLOW THERMISTOR
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
VOLTAGE MAINS IN AT PCB
{GAINPCBACS}
RESISTANCE FUSE MAINS
REMOVE THE FUSE FROM THE FUSED SPUR
OBSERVATION BOILER RESET (E2)
ENSURE BOILER IS COOL
INSPECTION CH FILTER
DRAIN BOILER PRIMARY CIRCUIT
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
FAULT CODES
FAULT CODES
INSPECTION PLATE HEAT EXCHANGER
DRAIN BOILER PRIMARY
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
INSPECTION CH FILTER
DRAIN BOILER PRIMARY CIRCUIT
INSPECTION PLATE HEAT EXCHANGER
DRAIN BOILER PRIMARY
VOLTAGE MAIN PCB TO DISPLAY PCB
REMOVE 4X SCREWS SEC
INSPECTION CH FILTER
DRAIN BOILER PRIMARY CIRCUIT
INSPECTION CH FILTER
DRAIN BOILER PRIMARY CIRCUIT
OBSERVATION WATER PRESSURE SWITCH
{GAINPCBACS}
RESISTANCE WATER PRESSURE SWITCH AND HARNESS (X9)
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE WATER PRESSURE SWITCH AND HARNESS (X13)
DISCONNECT CONNECTOR X13 FROM THE PCB
VOLTAGE EXTERNAL CONTROLS DHW INTO BOILER
{GAINPCBACS}
ANY DHW CONTROLS TURNED ON
VOLTAGE FLOW SWITCH TO PCB (NO DEMAND)
ENSURE NO DEMANDS
INSPECTION CH FILTER
DRAIN BOILER PRIMARY CIRCUIT
INSPECTION PLATE HEAT EXCHANGER
DRAIN BOILER PRIMARY
VOLTAGE FLOW SWITCH TO PCB (DHW ISOLATED)
ISOLATE DHW VALVE UN
INSPECTION CH FILTER
DRAIN BOILER PRIMARY CIRCUIT
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
VOLTAGE FAN PERMANENT AT PCB
{GAINPCBACS}
REMOVE FAN CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
VOLTAGE DC DEMAND TO FAN
{GAINPCBACS}
REMOVE FAN CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
RESISTANCE HARNESS FAN (24V)
DISCONNECT LOW VOLTAGE PLUG FROM FAN
DISCONNECT CONNECTOR X8 FROM THE PCB
COMBUSTION TEST
ATTACH FGA TO COMBUSTION TEST POINT
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET TEST POINT
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION AIR INTAKE
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION VENTURI
REMOVE FAN & BURNER ASSEMBLY
REMOVE AIR INTAKE FROM FAN & BURNER ASSEMBLY
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
OBSERVATION BOILER RESET (E1)
ENSURE BOILER IS COOL
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE POC SENSOR
DISCONNECT BOTH LEADS RUNNING FROM THE POC SENSOR
RESISTANCE HARNESS HEAT EXCHANGER FUSE
{GAINPCBACS}
DISC
OBSERVATION WATER PRESSURE SWITCH
{GAINPCBACS}
RESISTANCE WATER PRESSURE SWITCH AND HARNESS (X9)
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE WATER PRESSURE SWITCH AND HARNESS (X13)
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE HARNESS FAN (24V)
DISCONNECT LOW VOLTAGE PLUG FROM FAN
DISCONNECT CONNECTOR X8 FROM THE PCB
OBSERVATION LINK LOW VOLTAGE CONTROLS (CH)
REMOVE TWO WIRES AT
RESISTANCE HARNESS FLOW SWITCH
DISCONNECT PLUG FROM FLOW SWITCH
DISCONNECT X13 FROM THE PCB
OBSERVATION BOILER REACTS TO DHW WITH FLOW SWITCH MADE
UNCLIP THE FLOW SWIT
VOLTAGE EXTERNAL CONTROLS DHW INTO BOILER
{GAINPCBACS}
ANY DHW CONTROLS TURNED ON
RESISTANCE FAN AND HARNESS
DISCONNECT CONNECTOR X8 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS (FUSE INV)
{GAINPCBACS}
DISCONNECT CONNECTOR X1 FROM THE PCB
RESISTANCE SPARK GENERATOR AND HARNESS
DISCONNECT CONNECTOR X1 FROM THE PCB
RESISTANCE DIVERTER VALVE AND HARNESS
DISCONNECT CONNECTOR X5 FROM THE PCB
PRESSURE EXPANSION VESSEL
DRAIN BOILER PRIMARY CIRCUIT
FAULT CODES
FAULT CODES
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
OBSERVATION DIVERTER VALVE MOVEMENT
UNCLIP AND REMOVE DI
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT X5 FROM THE PCB
DISCONNECT PLUG FROM DIVERTER VALVE
OBSERVATION DIVERTER VALVE MOVEMENT DHW
UNCLIP AND REMOVE DI
OBSERVATION BURNER IGNITES AND ESTABLISHES
ENSURE APPLIANCE IS COOL
NO DEMANDS FOR DHW OR CH
OBSERVATION SPARKING AT SPARK GENERATOR
DISCONNECT IGNITION
RESISTANCE GAS VALVE AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X1 FROM THE PCB
PRESSURE FAN ON STARTUP
1. DISCONNECT
PRESSURE GAS INLET AND DROP
ATTACH U-GAUGE TO GAS INLET TEST POINT
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION AIR INTAKE
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
INSPECTION VENTURI
REMOVE FAN & BURNER ASSEMBLY
REMOVE AIR INTAKE FROM FAN & BURNER ASSEMBLY
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET TEST POINT
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION AIR INTAKE
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION VENTURI
REMOVE FAN & BURNER ASSEMBLY
REMOVE AIR INTAKE FROM FAN & BURNER ASSEMBLY
VOLTAGE RECTIFICATION DURING SELF CHECK
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET TEST POINT
RESISTANCE HARNESS SPARK GENERATOR
DISCONNECT X1 FROM T
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
RESISTANCE SPARK ELECTRODE
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION AIR INTAKE
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION VENTURI
REMOVE FAN & BURNER ASSEMBLY
REMOVE AIR INTAKE FROM FAN & BURNER ASSEMBLY
INSPECTION DIVERTER VALVE SPINDLE
UNCLIP AND REMOVE DIVERTER MOTOR FROM SPINDLE
VOLTAGE RECTIFICATION DURING SELF CHECK
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET TEST POINT
RESISTANCE HARNESS SPARK GENERATOR
DISCONNECT X1 FROM T
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
RESISTANCE SPARK ELECTRODE
REMOVE FAN & BURNER ASSEMBLY
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION AIR INTAKE
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION VENTURI
REMOVE FAN & BURNER ASSEMBLY
REMOVE AIR INTAKE FROM FAN & BURNER ASSEMBLY
RESISTANCE GAS VALVE AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X1 FROM THE PCB
RESISTANCE HARNESS SPARK GENERATOR
DISCONNECT X1 FROM T
OBSERVATION SPARKING AT SPARK GENERATOR
DISCONNECT IGNITION
RESISTANCE HARNESS SPARK GENERATOR
DISCONNECT X1 FROM T
OBSERVATION DIVERTER VALVE MOVEMENT
UNCLIP AND REMOVE DI
INSPECTION DIVERTER VALVE SPINDLE
UNCLIP AND REMOVE DIVERTER MOTOR FROM SPINDLE
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT X5 FROM THE PCB
DISCONNECT PLUG FROM DIVERTER VALVE
OBSERVATION DISCONNECT X8
{GAINPCBACS}
DISCONNECT X8 FROM THE PCB
RESISTANCE FUSE (PCB)
REMOVE FUSE FROM HOLDER (NEXT TO X6 ON PCB)
RESISTANCE HARNESS FAN (24V)
DISCONNECT LOW VOLTAGE PLUG FROM FAN
DISCONNECT CONNECTOR X8 FROM THE PCB
OBSERVATION DISCONNECT X8 (NO DISPLAY)
{GAINPCBACS}
DISCONNECT X8 FROM THE PCB
RESISTANCE HARNESS FAN (24V)
DISCONNECT LOW VOLTAGE PLUG FROM FAN
DISCONNECT CONNECTOR X8 FROM THE PCB
RESISTANCE SENSOR FLOW AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
RESISTANCE SENSOR RETURN AND HARNESS
DISCONNECT CONNECTOR X13 FROM THE PCB
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET TEST POINT
INSPECTION HEAT EXCHANGER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION BURNER
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION AIR INTAKE
BURNER & FAN ASSEMBLY REMOVED FROM APPLIANCE
INSPECTION VENTURI
REMOVE FAN & BURNER ASSEMBLY
REMOVE AIR INTAKE FROM FAN & BURNER ASSEMBLY
VOLTAGE EXTERNAL CONTROLS CH INTO BOILER (NO DEMAND)
{GAINPCBACS}
ENSURE NO DEMANDS
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT X5 FROM THE PCB
DISCONNECT PLUG FROM DIVERTER VALVE
INSPECTION FLOW SWITCH ASSEMBLY
ISOLATE MAINS WATER
System Information
- Total Tests: 588
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control