Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Attach U gauge to inlet pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow fan purge to complete (2 minutes).
Turn hot water tap ON.
Allow fan to run and ignition sequence to commence.
Observe the U gauge during the sparking stage of the ignition cycle, the pressure should dip slightly to indicate that the gas valve is opening.
Note:
When "U" gauge is removed test point should be tightened and checked for gas tightness.
Turn hot water tap ON.
Allow fan to run and ignition sequence to commence.
Observe the U gauge during the sparking stage of the ignition cycle, the pressure should dip slightly to indicate that the gas valve is opening.
Note:
When "U" gauge is removed test point should be tightened and checked for gas tightness.