Set Appliance State:

CH Demand
Boiler CH thermostat set to MAX
Ensure appliance is set to winter mode - NO sun symbol in display
(Press reset button briefly to toggle sun symbol on and off)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the burner to ignite and the boiler to start to heat the radiators, measure the temperature differential between the flow and return pipes to the primary heat exchanger.
Expect a differential of approximately 25°C or less.
Is the temperature differential as expected?
Note:
The differential measured on initial firing may be slightly higher, also this appliance can take a significant time to ramp up, only select an outcome on this test once the appliance has ramped up.