Set Appliance State:
CH Demand
Boiler CH thermostat set to MAX
Ensure appliance is set to winter mode - NO sun symbol in display
(Press reset button briefly to toggle sun symbol on and off)
Ensure appliance is set to winter mode - NO sun symbol in display
(Press reset button briefly to toggle sun symbol on and off)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the burner to ignite and the boiler to start to heat the radiators, measure the temperature differential between the flow and return pipes to the primary heat exchanger.
Expect a differential of approximately 15°C or less.
Is the temperature differential as expected?
Note:
The differential measured on initial firing may be slightly higher, also this appliance can take a significant time to ramp up, only select an outcome on this test once the appliance has ramped up.
Expect a differential of approximately 15°C or less.
Is the temperature differential as expected?
Note:
The differential measured on initial firing may be slightly higher, also this appliance can take a significant time to ramp up, only select an outcome on this test once the appliance has ramped up.