Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Remove the two spade connectors from the return thermistor

Measurement:

Measure the resistance between the two terminals on the return sensor.
Resistances vary with temperature and should conform approximately to the table below:
Temperature °CResistance in ohms
0-1028.8k - 19.0k
10-2019.0k - 12.0k
20-30 12.0k - 8.0k
30-40 8.0k - 5.0k
40-505.0k - 3.5k
50-603.5k - 2.5k
60-702.5k - 1.7k
70-801.7k - 1.2k
80-901.2k - 860
90-100860 - 700