Set Appliance State:
Mains Power Off
Ensure NO demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
This appliances incorporates a two minute fan and pump purge period. The boiler should then enter standby.
During this time the fan will run continuously and the pump will pulse on and off for 5 seconds at a time. When the purge period ends the fan should stop running and the pump should no longer pulse.
Does the appliance behave as described above?
Note:
This fan and pump purge cannot be cancelled and will commence every time the power is reinstated. Where possible this XSol model will carry out tests during this fan purge period or will leave the power to the appliance switched on where safe to do so.
During this time the fan will run continuously and the pump will pulse on and off for 5 seconds at a time. When the purge period ends the fan should stop running and the pump should no longer pulse.
Does the appliance behave as described above?
Note:
This fan and pump purge cannot be cancelled and will commence every time the power is reinstated. Where possible this XSol model will carry out tests during this fan purge period or will leave the power to the appliance switched on where safe to do so.