Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
DHW Demand
DHW Selector in Maximum (+) position
CH Selector in Minimum (-) position
ON/OFF Switch in ON position
Drop the facia and remove the 6 screws from the PCB housing
Turn over housing to reveal the PCB
Use electrical insulating mat
DHW Demand
DHW Selector in Maximum (+) position
CH Selector in Minimum (-) position
ON/OFF Switch in ON position
Drop the facia and remove the 6 screws from the PCB housing
Turn over housing to reveal the PCB
Use electrical insulating mat
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Measure for AC volts on connections 2 and 3 on Plug X8,
best contact can be made on the terminals direct on the PCB.
Expect approx. 2 V AC with DHW demand.
Remove the demand and the voltage should fall to approx. 0 V AC.
Notes:
Place the probes in the small holes on the PCB.
Ensure a good contact is made otherwise misdiagnosis will occur.
If in doubt repeat the test.
best contact can be made on the terminals direct on the PCB.
Expect approx. 2 V AC with DHW demand.
Remove the demand and the voltage should fall to approx. 0 V AC.
Notes:
Place the probes in the small holes on the PCB.
Ensure a good contact is made otherwise misdiagnosis will occur.
If in doubt repeat the test.

Isolate as per TOPs P4
and refit as necessary