Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure for DC voltage across pin14 of connector X2 and a suitable earth connection.
The voltage measured will vary according to the primary system pressure but should conform approximately to the table below;
Is the voltage measured representative of the system pressure displayed on the manual gauge?
The voltage measured will vary according to the primary system pressure but should conform approximately to the table below;
| Voltage (DC) | Approx. system pressure (bar) |
| 1.2 | 0 |
| 1.7 | 1 |
| 2.2 | 2 |
| 2.8 | 3 |
Is the voltage measured representative of the system pressure displayed on the manual gauge?

Isolate as per TOPs P4
and refit as necessary