Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature clamps to the flow and return pipes as indicated by the red arrows ensuring a good contact
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to run for central heating and the system to begin to heat.
Measure the temperature differential.
Expect a differential of approximately 25°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly to provide correct test results.
2. Initial temperature differential may be greater than 25°C when system is heated from cold.
Measure the temperature differential.
Expect a differential of approximately 25°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly to provide correct test results.
2. Initial temperature differential may be greater than 25°C when system is heated from cold.