ARISTON CLAS ONE / CLAS NET ONE / E-COMBI ONE
GLOBALLY REPLACED
OBSERVATION FAN RUNS
GAIN ACCESS TO THE FAN
HEADER FOR FUSE INVESTIGATION
OK TO BE BLANK
HEADER FOR OVERHEAT FAULT CODE 101
OK TO BE BLANK
HEADER FOR CH FLOW TEMP PROBE ERROR FAULT CODE 110
OK TO BE BLANK
HEADER FOR LOW PRESSURE FAULT CODE 108
OK TO BE BLANK
HEADER FOR EXTERNAL SENSOR ERROR FAULT CODE 114
OK TO BE BLANK
HEADER FOR FLOOR THERMOSTAT CONTACT OPEN FAULT CODE 116
OK TO BE BLANK
HEADER FOR COMMUNICATION ERROR FAULT CODE 302
OK TO BE BLANK
HEADER FOR FLAME DETECTED GAS VALVE CLOSED FAULT CODE 502
OK TO BE BLANK
HEADER FOR FAN FAULT CODE 604 AND 612
OK TO BE BLANK
HEADER FOR TOO MANY RESETS ERROR CODE 304
OK TO BE BLANK
OBSERVATION APPLIANCE SELF CHECK
NO DEMANDS
HEADER FOR CH RETURN TEMP PROBE ERROR CODE 112
OK TO BE BLANK
HOW TO ACTIVATE TEST FUNCTION
ALLOW FOR SELF CHECK TO COMPLETE
OBSERVATION DHW DEMAND RECOGNISED
TURN HOT WATER TAP ON WITH A FLOW RATE OF 3 L/MIN
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT
LITE DIAGNOSTIC
DIAGNOSIS RELIES ON
QUICK ACCESS DATA AND INFORMATION
THE TABLE BELOW SHOW
HEADER FOR QADAI FLOW TEMP PROBE
OK TO BE BLANK
HEADER FOR QADAI RETURN TEMPERATURE PROBE
OK TO BE BLANK
HEADER FOR QADAI GAS VALVE RESISTANCE
OK TO BE BLANK
HEADER FOR QADAI GAS VALVE VOLTAGE
OK TO BE BLANK
HEADER FOR QADAI PUMP RESISTANCE
OK TO BE BLANK
HEADER FOR QADAI PUMP VOLTAGE
OK TO BE BLANK
HEADER FOR QADAI FAN RESISTANCE
OK TO BE BLANK
HEADER FOR QADAI DHW REED SENSOR VOLTAGE
OK TO BE BLANK
HEADER FOR QADAI STEPPER MOTOR RESISTANCE
OK TO BE BLANK
HEADER FOR QADAI STEPPER MOTOR VOLTAGE
OK TO BE BLANK
HEADER FOR SCHED SERVICE CALL 3P9
OK TO BE BLANK
HEADER FOR HIGH PRESSURE ERROR CODE 109
OK TO BE BLANK
HEADER FOR PARAMETER 2-4-7 SET INCORRECTLY ERROR CODE 102
OK TO BE BLANK
ERROR CODE 612
CABLE FAN
PARAMETER INFO
Z REDIRECTION
ERROR CODE 304
PCB MAIN
ERROR CODE 302
PCB MAIN
ERROR CODE 302
WIRING - DISPLAY
ERROR CODES 1
Z REDIRECTION
NO DISPLAY
FUSE (FUSED SPUR)
CIRCULATION ERROR CODES
TEMPERATURE PROBE FITMENT
CIRCULATION ERROR CODES
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
CIRCULATION ERROR CODES
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
ERROR CODE 502
GAS VALVE
TEST FUNCTION ACTIVATION
Z REDIRECTION
PARAMETERS
Z REDIRECTION
BURNER DOES NOT IGNITE
CABLE GAS VALVE AND PCB MAIN
BURNER DOES NOT IGNITE
GAS VALVE & PCB - MAIN
POOR FLOW RATE
TAP - COLD WATER
POOR FLOW RATE
COLD WATER SUPPLY
TOO LOW
GAS PRESSURE INLET
FAN NOT RUNNING
CABLE FAN
DHW RUNS HOT THEN COLD
SYSTEM PRESSURE
CASE REMOVAL
Z REDIRECTION
PUMP NOT RUNNING FAULT CODE 102
PCB MAIN
PUMP NOT RUNNING FAULT CODE 102
CABLE - PUMP TACO
REACHES TEMP RADS COOL
TAP - SERVICE
INSUFFICIENT CIRCULATION FAULT CODE
TAP - SERVICE
CIRCULATION ISSUES
EXCHANGER (MAIN)
CIRCULATION ERROR CODES
BY-PASS
CIRCULATION ERROR CODES
WATER FILTER
CIRCULATION ERROR CODES
PUMP 5M PWM TACO
OVERHEAT
SYSTEM PRESSURE
OVERHEAT
PRESSURE GAUGE
OVERHEAT FAULT CODE
TAP - SERVICE
FOR TYPE DIAG PROCEDURE
Z REDIRECTION
BOILER TO TEMP RADS COOL
PUMP 5M PWM TACO
CIRCULATION ERROR CODES
SYSTEM PRESSURE
INSUFFICIENT CIRC
PRESSURE GAUGE
FAULT CODE 502
GAS VALVE
BURNER DOES NOT IGNITE
EXCHANGER (MAIN)
DOES NOT IGNITE
FLUE
PARAMETER GUIDE
Z REDIRECTION
NO DISPLAY
FUSE 250V 2A
BURNER DOES NOT ESTABLISH
CONDENASTE TRAP
ERROR CODE 612
FAN ASSEMBLY
FAULT CODE 108
SYSTEM PRESSURE
FAULT CODE 108
PRESSURE GAUGE
FAULT CODE 108
PARAMETER DEVICE INDICATOR FOR HEATING CIRCUIT PRESSURE
BLANK DISPLAY
PCB MAIN
BLANK DISPLAY
WIRING - DISPLAY
BLANK FOR LITE DIAGNOSTIC
Z REDIRECTION
BLANK FOR QADAI
Z REDIRECTION
NOT RUNNING WITH DEMAND
FAN ASSEMBLY
NOT SENSING DEMAND
3- WAY VALVE CABLE (DIVERTER STEPPER / REED SWITCH AND LWPS HARNESS)
SET INCORRECTLY
PARAMETER APPLIANCE VERSION
ERROR CODE 108
3- WAY VALVE CABLE (DIVERTER STEPPER / REED SWITCH AND LWPS HARNESS)
IGNITES BUT DOES NOT ESTABLISH
SILENCER
BURNER IGNITES BUT DOES NOT ESTABLISH
IGNITION ELECTRODE
DHW NOT RECOGNISED
FLOW METER MAGNET
DHW TOO HOT
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
DHW TOO HOT
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
NO PUMP OVERRUN
PCB MAIN
POOR DHW TEMP RISE
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
POOR DHW TEMP RISE
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
POOR DHW TEMP RISE
PUMP 5M PWM TACO
POOR DHW TEMP RISE
EXTERNAL MIXING
POOR DHW TEMP RISE
WATER FILTER
FAILED GAS RATE POOR DHW TEMP
SILENCER
FAILED GAS RATE POOR DHW TEMP
CONDENASTE TRAP
POOR DHW TEMP RISE
SYSTEM PRESSURE
POOR HW
PARAMETER DHW POWER
DHW RUNS HOT THEN COLD
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
DHW RUNS HOT THEN COLD
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
DHW RUNS HOT THEN COLD
PUMP 5M PWM TACO
DHW RUNS HOT THEN COLD
WATER FILTER
DHW RUNS HOT THEN COLD
TEMPERATURE PROBE FITMENT
SET TEMP NOT REACHED
PARAMETER HEATING POWER
FAILS TO REACH SET TEMP
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
FAILS TO REACH SET TEMP
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
FAILS TO REACH SET TEMP
SYSTEM PRESSURE
ERROR CODE 502
IGNITION ELECTRODE
ERROR CODE 116
UNDERFLOOR HEATING THERMOSTAT LINK
FUSE INVESTIGATION
FAN ASSEMBLY
FUSE INVESTIGATION
CABLE - PUMP TACO
TEMP PROBE ERROR CODE
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
TEMP PROBE ERROR CODE
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
PCB ERROR CODE
PCB MAIN
OVERHEAT
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
OVERHEAT
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
PUMP NOT RUNNING FAULT CODE 101
PCB MAIN
PUMP NOT RUNNING FAULT CODE 101
CABLE - PUMP TACO
OVERHEAT
PUMP 5M PWM TACO
PUMP OVERRUN NOT WORKING
PCB MAIN
OVERHEAT
EXCHANGER (MAIN)
OVERHEAT
BY-PASS
OVERHEAT
WATER FILTER
OVERHEAT ERROR CODE
TEMPERATURE PROBE FITMENT
OVERHEAT 101 ERROR
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
OVERHEAT ERROR 101
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
QADAI
GAS VALVE
QADAI PUMP RESISTANCE
PUMP 5M PWM TACO
QADAI FAN RESISTANCE
FAN ASSEMBLY
QADAI
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
QADAI
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
QADAI GAS VALVE VOLTAGE
PCB MAIN
QADAI PUMP VOLTAGE
PCB MAIN
QADAI
REED SENSOR
QADAI
MOTOR - 3 WAY VALVE
QADAI STEPPER
PCB MAIN
CODE 3P9
PCB MAIN
FAULT CODE 109
PARAMETER DEVICE INDICATOR FOR HEATING CIRCUIT PRESSURE
ERROR CODE 116
UNDERFLOOR HEATING THERMOSTAT
ERROR CODE 102
PARAMETER DEVICE INDICATOR FOR HEATING CIRCUIT PRESSURE
PUMP NOT RUNNING
PCB MAIN
PUMP NOT RUNNING
CABLE - PUMP TACO
PUMP DOES NOT RUN
PUMP 5M PWM TACO
NO FAN VOLATGE
PCB MAIN
FAN NOT RUNNING
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
FAN NOT RUNNING
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
ERROR CODE 612
PCB MAIN
ERROR CODE 604 / 612
PCB MAIN
FUSE GONE
TIMECLOCK
FUSE INVESTIGATION
GAS VALVE
USER DISPLAY GUIDE
Z REDIRECTION
DOES NOT RESPOND TO CH DEMAND
PCB MAIN
DOES NOT RESPOND TO CH DEMAND 6
PCB MAIN
DOES NOT RESPOND TO CH DEMAND 5
PCB MAIN
BURNER IGNITES BUT BAFFLES
CONDENASTE TRAP
NOT RESPONDING TO CH
PCB MAIN
NOT RESPONDING TO CH 1
PCB MAIN
NOT RESPONDING TO CH 2
PCB MAIN
ON WITH NO DEMAND
CABLE - PUMP TACO
FIRES WITH NO DEMAND
PROBE - TEMPERATURE - C/W CLIP KIT (FLOW)
FIRES WITH NO DEMAND
PROBE - TEMPERATURE - C/W CLIP KIT (RETURN)
ON WITH NO DEMAND EBUS
PCB MAIN
ON WITH NO DEMAND
PCB MAIN
MAGNET STUCK ON NO DEMAND
FLOW METER MAGNET
DHW ON WITH NO DEMAND
PCB MAIN
FAULT CODE HISTORY
Z REDIRECTION
NO PRESSURE DROP OBSERVED
GAS VALVE
BURENR DOES NOT IGNITE 1
SILENCER
SET INCORRECTLY START UP
PARAMETER APPLIANCE VERSION
NO POWER TO DIVERTER MOTOR
PCB MAIN
OPEN CIRCUIT MOTOR NOT MOVING TO CH POSITION
3- WAY VALVE CABLE (DIVERTER STEPPER / REED SWITCH AND LWPS HARNESS)
SEIZED
MOTOR - INCLUDING 3 WAY SPRING VALVE KIT
REACHES TEMP RADS COOL
BY-PASS
REACHES TEMP RADS COOL
WATER FILTER
NO VOLTAGE TO DIVERTER MOTOR
PCB MAIN
OPEN CIRCUIT MOTOR NOT MOVING TO DHW POSITION
3- WAY VALVE CABLE (DIVERTER STEPPER / REED SWITCH AND LWPS HARNESS)
RADS HEATING WITH DH DEMAND
MOTOR - INCLUDING 3 WAY SPRING VALVE KIT
BURNER IGNITES BUT BAFFLES
SILENCER
BURNER DOES NOT IGNITE
CONDENASTE TRAP
BURNER DOES NOT IGNITE 1
IGNITION ELECTRODE
BURNER DOES NOT IGNITE
VENTURI
BURNER ESTABLISHES THEN BAFFLES
GAS PRESSURE INLET
REACHES TEMP RADS COOL
SYSTEM PRESSURE
EXCESSIVE SYSTEM PRESSURE RISE
VESSEL - EXPANSION
BURNER IGNITES BUT DOES NOT ESTABLISH
GAS PRESSURE INLET
ERROR CODE 114
PCB MAIN
FAULT CODE 114
PCB MAIN
ERROR CODE 303 RESETS CONFIRM BOILER OP
Z REDIRECTION
ERROR CODE 302
PCB - DISPLAY
ERROR CODES
Z REDIRECTION
FUSE FURTHER INVESTIGATION
Z REDIRECTION
TEMP PROBE ERRPR CODE
PCB MAIN
ERROR CODE 110
PCB MAIN
BURNER DOES NOT IGNITE 2
PCB MAIN
POOR FLOW RATE
SANITARY HEAT EXCHANGER
PASSING
MOTOR - INCLUDING 3 WAY SPRING VALVE KIT
POOR FLOW RATE
FLOW METER (DHW FILTER)
SEIZED FAULT CODE 102
PUMP 5M PWM TACO
CIRCULATION ISSUES
SANITARY HEAT EXCHANGER
CIRCULATION ERROR CODES
PCB MAIN
NOT SENSING DEMAND
PCB MAIN
ERROR CODE 502
PCB MAIN
BURNER DOES NOT IGNITE
GAS VALVE
FUSE FURTHER INVESTIGATION 1
Z REDIRECTION
FAULT CODE 108
PCB MAIN
DHW DEMAND NOT RECOGNISED
REED SENSOR
ERROR CODE 201 OR 203
PCB MAIN
ERROR CODE 108
LOW PRESSURE SWITCH
FAULT CODE 108
PUMP MANIFOLD
FAULT CODE 108
LOW PRESSURE SWITCH
BURNER DOES NOT IGNITE
IGNITION ELECTRODE
BURNER DOES NOT IGNITE
EARTH WIRE
NOT SPARKING
PCB MAIN
DOES NOT ESTABLISH
EXCHANGER (MAIN)
BURNER IGNITES BUT BAFFLES
BURNER
BURNER IGNITES BUT BAFFLES
EXCHANGER (MAIN)
BURNER IGNITES BUT BAFFLES
VENTURI
POOR FLOW RATE
FLOW METER MAGNET
DHW TOO HOT
PCB MAIN
POOR DHW TEMP RISE
SANITARY HEAT EXCHANGER
POOR DHW TEMP RISE
EXCHANGER (MAIN)
POOR DHW TEMP RISE
PCB MAIN
FAILED GAS RATE POOR DHW TEMP
VENTURI
FAILED GAS RATE POOR DHW TEMP
FAN ASSEMBLY
FAILED GAS RATE POOR DHW TEMP
GAS VALVE
FAILED GAS RATE POOR DHW
BURNER
FAILED GAS RATE POOR DHW TEMP
EXCHANGER (MAIN)
DHW RUNS HOT THEN COLD
PCB MAIN
RESTRICTED DHW RUNS HOT THEN COLD
SANITARY HEAT EXCHANGER
RESTRICTED DHW RUNS HOT THEN COLD
EXCHANGER (MAIN)
BOILER TEMP LOW SYSTEM TEMP LOW
PCB MAIN
FUSE INVESTIGATION
CABLE FAN
FUSE INVESTIGATION
PUMP 5M PWM TACO
ERROR CODE 110
NTC - CABLE
ERROR CODE 112
NTC - CABLE
OVERHEAT
PCB MAIN
SEIZED FAULT CODE 101
PUMP 5M PWM TACO
OVERHEAT
SANITARY HEAT EXCHANGER
OVERHEAT FAULT CODE
OVERHEAT
FAULT CODE 101
PCB MAIN
OVERHEAT 101
PCB MAIN
SENSOR TEMP FLOW
RESULT AS EXPECTED
SENSOR TEMP RETURN
RESULT AS EXPECTED
GAS VALVE RESISTANCE
RESULT AS EXPECTED
GAS VALVE VOLTAGE
RESULT AS EXPECTED
PUMP RESISTANCE
RESULT AS EXPECTED
PUMP VOLTAGE
RESULT AS EXPECTED
FAN RESISTANCE
RESULT AS EXPECTED
REED SENSOR
RESULT AS EXPECTED
STEPPER RESISTANCE
RESULT AS EXPECTED
STEPPER VOLTAGE
RESULT AS EXPECTED
CODE 3P9
MAINTENANCE INTERVAL SURPASSED
ERROR 109
PCB MAIN
ERROR CODE 102
PCB MAIN
SEIZED
PUMP 5M PWM TACO
PUMP DOES NOT RUN
PCB MAIN
FAN DOES NOT RUN
FAN ASSEMBLY
FAN NOT RUNNING
PCB MAIN
FAULT CODE 612
FAN ASSEMBLY
FUSE INVESTIGATION
PCB - MAIN (FUSE BLOWN)
FUSE INVESTIGATION
CABLE GAS VALVE
DOES NOT RESPOND TO CH DEMAND
EBUS CONTROLS
DOES NOT RESPOND TO CH DEMAND 2
PCB MAIN
DOES NOT RESPOND TO CH DEMAND 2
EBUS CONTROLS
DOES NOT RESPOND TO CH DEMAND 4
PCB MAIN
DOES NOT RESPOND TO CH DEMAND 1
EBUS CONTROLS
DOES NOT RESPOND TO CH DEMAND 3
PCB MAIN
NOT RESPONDING TO CH
TIMECLOCK
NOT RESPONDING TO CH 1
TIMECLOCK
NOT RESPONDING TO CH 2
TIMECLOCK
NO DEMAND SHOWING BUT PUMP RUNNING
PCB MAIN
APPLIANCE FIRES WITH NO DEMAND
FROST PROTECTION
FIRES WITH NO DEMAND 1
PCB MAIN
ON WITH NO DEMAND
EBUS CONTROLS
DRIPPING TAP
DHW SYSTEM
ON WITH NO DEMAND
REED SENSOR
BAFFLES OR IS NOISY
GAS VALVE
BURNER DOES NOT IGNITE 1
CABLE GAS VALVE
BURNER DOES NOT IGNITE 1
GAS VALVE
DOES NOT IGNITE
BURNER
BURNER DOES NOT IGNITE 1
EXCHANGER (MAIN)
BURNER DOES NOT IGNITE 1
VENTURI
BLANK DISPLAY
PCB - DISPLAY
---- ON DISPLAY
PCB MAIN
NOT MOVING TO CH POSITION
MOTOR - 3 WAY VALVE
NOT MOVING TO DHW POSITION
MOTOR - 3 WAY VALVE
BURNER DOES NOT IGNITE
GAS PRESSURE INLET
BURNER DOES NOT IGNITE
BURNER
DOES NOT IGNITE
IGNITION ELECTRODE
EXCESSIVE PRESSURE RISE
PIPE - EXPANSION VESSEL
ERROR CODE 114
EXTERNAL SENSOR
FAULT CODE 116
PCB MAIN
ERROR CODE 116
PCB MAIN
ERROR CODE SHOWN
CHARACTERISTIC TEST FROM OBSERVATION APPLIANCE SELF CHECK
DISPLAY DOES NOT OPERATE
CHARACTERISTIC TEST FROM OBSERVATION APPLIANCE SELF CHECK
APPLIANCE REACHES TEMP RADIATORS REMAIN COOL OR DO NOT HEAT
CHARACTERISTIC TEST FROM OPERATION CH
APPLIANCE AND RADIATORS FAIL TO REACH SET TEMPERATURE
CHARACTERISTIC TEST FROM OPERATION CH
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
TEMPERATURE RISE UNSATISFACTORY, RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM OPERATION DHW
TEMPERATURE RISE UNSATISFACTORY, RADIATORS HEAT WITH NO DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT THEN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
FILTER RESTRICTED OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION FLOW METER ASSEMBLY
MAGNET RESTRICTED, BLOCKED OR JAMMED
CHARACTERISTIC TEST FROM INSPECTION FLOW METER ASSEMBLY
APPLIANCE DOES NOT RESPOND TO A CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH
PUMP RUNS OR APPLIANCE ATTEMPS TO FIRE
CHARACTERISTIC TEST FROM OBSERVATION APPLIANCE SELF CHECK
PUMP MANIFOLD BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SWITCH AND MANIFOLD
LOW PRESSURE SENSOR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION LOW PRESSURE SWITCH AND MANIFOLD
IGNITION ELECTRODE AND LEAD UNSATISFACTORY
CHARACTERISTIC TEST FROM RESISTANCE IGNITION ELECTRODE, LEAD AND EARTH WIRE
EARTH WIRE UNSATISFACTORY
CHARACTERISTIC TEST FROM RESISTANCE IGNITION ELECTRODE, LEAD AND EARTH WIRE
BURNER RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION BURNER AND SPARK GAP
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
AIR / GAS MIXER (VENTURI) RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
BURNER RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION BURNER AND SPARK GAP
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
AIR / GAS MIXER (VENTURI) RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
TEMPERATURE DIFFERENTIAL STILL EXCESSIVE
CHARACTERISTIC TEST FROM RESISTANCE IGNITION ELECTRODE, LEAD AND EARTH WIRE
APPLIANCE DOES NOT RESPOND TO A CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH
AIR GAS MIXER RESTRICTED AND / OR BLOCKED / IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER AND FAN ASSEMBLY
FAN RESTRICTED AND / OR BLOCKED / IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER AND FAN ASSEMBLY
BURNER RESTRICTED / BLOCKED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION BURNER AND PRIMARY HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
TEMPERATURE DIFFERENTIAL STILL EXCESSIVE
CHARACTERISTIC TEST FROM RESISTANCE IGNITION ELECTRODE, LEAD AND EARTH WIRE
APPLIANCE DOES NOT RESPOND TO A CH DEMAND
CHARACTERISTIC TEST FROM OPERATION CH
APPLIANCE CONTINUES TO HEAT BEYOND 82 °C
CHARACTERISTIC TEST FROM OBSERVATION DOES OVERHEAT OCCUR AT MAX TEMPERATURE
APPLIANCE OVERHEATS BEFORE 82 °C IS REACHED
CHARACTERISTIC TEST FROM OBSERVATION DOES OVERHEAT OCCUR AT MAX TEMPERATURE
CH DEMAND ACTIVATED
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY
FROST PROTECTION ACTIVATED
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY
NO DEMAND SHOWING
CHARACTERISTIC TEST FROM OBSERVATION DISPLAY
BURNER RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION BURNER AND SPARK GAP
HEAT EXCHANGER FLUEWAYS RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
AIR / GAS MIXER (VENTURI) RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
-- -- ON DHW SIDE OF THE DISPLAY
CHARACTERISTIC TEST FROM OBSERVATION APPLIANCE SELF CHECK
NO PRESSURE DROP OBSERVED
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
INLET PRESSURE LOW OR DIES AWAY DURING IGNITION
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
BURNER RESTRICTED AND / OR IN POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION BURNER AND SPARK GAP
SPARK GAP UNSATISFACTORY
CHARACTERISTIC TEST FROM INSPECTION BURNER AND SPARK GAP
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION DOES BURNER IGNITE AND ESTABLISH
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION DOES BURNER IGNITE AND ESTABLISH
BURNER IGNITES AND ESTABLISHES BUT BAFFLES OR IS NOISY
CHARACTERISTIC TEST FROM OBSERVATION DOES BURNER IGNITE AND ESTABLISH
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
01/06/2023 15:28:03 2211_1_50_1 21/06/2023 10:41:52
05/06/2023 14:51:31
RESISTANCE HARNESS FAN
REMOVE THE CONNECTOR FROM THE FAN
VOLTAGE TO DISPLAY PCB
{GAINPCBACS}
REMOVE DISPLAY HARNESS CONNECTOR (5 BLUE WIRE) FROM
THE MAIN PCB AND MAKE SAFE
RESISTANCE FUSE (FUSED SPUR)
REMOVE FUSE FROM FUSED SPUR
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
RESISTANCE RETURN TEMPERATURE PROBE
REMOVE THE SIDE PANEL
REMOVE THE LEADS FROM THE RETURN TEMPERATURE PROBE (BLUE LEADS)
RESISTANCE FLOW TEMPERATURE PROBE
REMOVE THE LEADS FROM THE FLOW TEMPERATURE PROBE (REDS LEADS)
RESISTANCE HARNESS FAN
REMOVE THE CONNECTOR FROM THE FAN
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL MAIN HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION INTERNAL BYPASS
APPLIANCE DRAINED AN
VOLTAGE DHW REED SENSOR - DEMAND
{GAINPCBACS}
RESISTANCE REED SENSOR HARNESS
DISCONNECT THE CONNECTOR FROM THE REED SENSOR
OBSERVATION RESET APPLIANCE - OVERHEAT
ENSURE APPLIANCE IS COOL
RESISTANCE LOW PRESSURE SWITCH HARNESS
REMOVE / LOOSEN RIGHT HAND SIDE PANEL
DISCONNECT THE CONNECTOR FROM THE WATER PRESSURE SWITCH
RESISTANCE IGNITION ELECTRODE, LEAD AND EARTH WIRE
REMOVE THE IGNITION
TEMPERATURE DIFFERENTIAL MAIN HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION SILENCER
REMOVE THE SILENCER
TEMPERATURE DIFFERENTIAL MAIN HEAT EXCHANGER
ATTACH TEMPERATURE C
RESISTANCE FAN AND HARNESS - FUSE INVESTIGATION
REMOVE CONNECTOR CN11 FROM THE PCB
RESISTANCE FAN - FUSE INVESTIGATION
REMOVE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE HARNESS PUMP
UNPLUG THE ELECTRICAL CONNECTOR FROM THE PUMP ASSEMBLY
RESISTANCE FLOW TEMPERATURE PROBE
REMOVE THE LEADS FROM THE FLOW TEMPERATURE PROBE (REDS LEADS)
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL MAIN HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION INTERNAL BYPASS
APPLIANCE DRAINED AN
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
REMOVE GAS VALVE CONNECTOR FROM THE PCB AND MAKE SAFE
RESISTANCE PUMP AND HARNESS
REMOVE CONNECTOR CN22 FROM THE PCB
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE FAN
REMOVE CONNECTOR FROM THE FAN ASSEMBLY
VOLTAGE DHW REED SENSOR - DEMAND
{GAINPCBACS}
RESISTANCE STEPPER MOTOR AND HARNESS (QADAI)
REMOVE CONNECTOR CN31 FROM THE PCB
VOLTAGE STEPPER MOTOR
{GAINPCBACS}
DISCONNECT PUMP SPEED CONTROL CONNECTOR
{GAINPCBACS}
REMOVE CONNECTOR CN25 (PUMP SPEED CONTROL) FROM THE PCB AND MAKE SAFE
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
DISCONNECT EXTERNAL CONTROLS (BUS)
REMOVE CONNECTOR BUS FROM THE PCB
DISCONNECT EXTERNAL CONTROLS (BUS)
REMOVE CONNECTOR BUS FROM THE PCB
DISCONNECT EXTERNAL CONTROLS (BUS)
REMOVE CONNECTOR BUS FROM THE PCB
BYPASS INTERNAL CLOCK
GAIN ACCESS TO INTER
BYPASS INTERNAL CLOCK
GAIN ACCESS TO INTER
BYPASS INTERNAL CLOCK
GAIN ACCESS TO INTER
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
DISCONNECT EXTERNAL CONTROLS (BUS) - SELF CHECK
REMOVE CONNECTOR BUS
OBSERVATION REMOVE REED SENSOR CONNECTOR
REMOVE CONNECTOR FROM THE REED SENSOR AND MAKE SAFE
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
INSPECTION DIVERTER VALVE BODY
ROTATE THE LOCKING R
INSPECTION DIVERTER VALVE BODY
ROTATE THE LOCKING R
RESISTANCE GAS VALVE HARNESS
REMOVE GAS VALVE CONNECTOR FROM THE PCB
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
OBSERVATION EXTERNAL SENSOR
{GAINPCBACS}
RESISTANCE UNDERFLOOR HEATING THERMOSTAT LINK
{GAINPCBACS}
REMOVE UNDERFLOOR HEATING CONNECTOR MARKED TA2 / FLOOR
RESISTANCE FAN
REMOVE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE HARNESS DISPLAY PCB
DISCONNECT THE DISPL
VOLTAGE MAINS POWER INPUT AT PCB
{GAINPCBACS}
RESISTANCE FUSE PCB
REMOVE FUSE FROM PCB
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
PRESSURE STANDING RETURN
ATTACH PRESSURE GAUG
RESISTANCE GAS VALVE
REMOVE THE ELECTRICAL CONNECTOR FROM THE GAS VALVE
INSPECTION FLOW METER ASSEMBLY
ISOLATE THE COLD WAT
RESISTANCE FLOW TEMPERATURE PROBE
REMOVE THE LEADS FROM THE FLOW TEMPERATURE PROBE (REDS LEADS)
RESISTANCE FAN
REMOVE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE HARNESS PUMP
UNPLUG THE ELECTRICAL CONNECTOR FROM THE PUMP ASSEMBLY
TEMPERATURE DIFFERENTIAL SECONDARY HEAT EXCHANGER
ATTACH TEMPERATURE C
TEMPERATURE DIFFERENTIAL MAIN HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION CH FILTER
APPLIANCE DRAINED AN
RESISTANCE IGNITION ELECTRODE AND LEAD
REMOVE THE IGNITION ELECTRODE FROM THE BURNER DOOR
DISCONNECT THE IGNITION LEAD FROM THE PCB
RESISTANCE IGNITION ELECTRODE AND LEAD
REMOVE THE IGNITION ELECTRODE FROM THE BURNER DOOR
DISCONNECT THE IGNITION LEAD FROM THE PCB
RESISTANCE LOW PRESSURE SWITCH AND HARNESS
REMOVE CONNECTOR CN31 FROM THE PCB
VOLTAGE TO DISPLAY PCB
{GAINPCBACS}
REMOVE DISPLAY HARNESS CONNECTOR (5 BLUE WIRE) FROM
THE MAIN PCB AND MAKE SAFE
RESISTANCE HARNESS DISPLAY PCB
DISCONNECT THE DISPL
VOLTAGE FAN
{GAINPCBACS}
ENSURE NO DEMANDS
INSPECTION FLOW METER MAGNET
ISOLATE THE COLD WAT
INSPECTION LOW PRESSURE SWITCH AND MANIFOLD
APPLIANCE DRAINED AN
INSPECTION SILENCER
REMOVE THE SILENCER
INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
REMOVE BURNER DOOR ASSEMBLY C/W FAN AND AIR / GAS MIXER
INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
REMOVE BURNER DOOR ASSEMBLY C/W FAN AND AIR / GAS MIXER
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
TEMPERATURE DIFFERENTIAL SECONDARY HEAT EXCHANGER
ATTACH TEMPERATURE C
APPLIANCE OUTPUT
TURN HOT WATER TAP O
INSPECTION CH FILTER
APPLIANCE DRAINED AN
INSPECTION AIR / GAS MIXER AND FAN ASSEMBLY
REMOVE FAN AND AIR / GAS MIXER (VENTURI)
INSPECTION BURNER AND PRIMARY HEAT EXCHANGER FLUEWAYS
THE BURNER DOOR ASSEMBLY SHOULD ALREADY BE REMOVED FROM PREVIOUS TEST
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
TEMPERATURE DIFFERENTIAL SECONDARY HEAT EXCHANGER
ATTACH TEMPERATURE C
INSPECTION CH FILTER
APPLIANCE DRAINED AN
RESISTANCE FLOW TEMPERATURE PROBE AND HARNESS
REMOVE 8 PIN CONNECTOR FROM THE PCB
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
RESISTANCE PUMP AND HARNESS
REMOVE CONNECTOR CN22 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE GAS VALVE CONNECTOR FROM THE PCB
VOLTAGE FAN
{GAINPCBACS}
ENSURE NO DEMANDS
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
RESISTANCE HARNESS PUMP
UNPLUG THE ELECTRICAL CONNECTOR FROM THE PUMP ASSEMBLY
TEMPERATURE DIFFERENTIAL SECONDARY HEAT EXCHANGER
ATTACH TEMPERATURE C
TEMPERATURE DIFFERENTIAL MAIN HEAT EXCHANGER
ATTACH TEMPERATURE C
OBSERVATION DOES OVERHEAT OCCUR AT MAX TEMPERATURE
ATTACH A TEMPERATURE CLAMP TO THE FLOW PIPE
INSPECTION CH FILTER
APPLIANCE DRAINED AN
RESISTANCE FLOW TEMPERATURE PROBE
REMOVE THE LEADS FROM THE FLOW TEMPERATURE PROBE (REDS LEADS)
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
VOLTAGE PUMP - CONTROL VOLTAGE
{GAINPCBACS}
ENSURE NO DEMANDS PRESENT
RESISTANCE HARNESS PUMP
UNPLUG THE ELECTRICAL CONNECTOR FROM THE PUMP ASSEMBLY
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
RESISTANCE INTERNAL TIMECLOCK - FUSE INVESTIGATION
GAIN ACCESS TO INTERNAL TIMECLOCK
BYPASS EXTERNAL CONTROLS
REMOVE ALL EXTERNAL
BYPASS EXTERNAL CONTROLS
REMOVE ALL EXTERNAL
BYPASS EXTERNAL CONTROLS
REMOVE ALL EXTERNAL
OBSERVATION DISPLAY
ENSURE NO DEMANDS
OBSERVATION ISOLATE COLD FEED TO APPLIANCE
ISOLATE THE COLD MAINS SUPPLY
(TURN THE LEVER 90° CLOCKWISE UNTIL HORIZONTAL)
TEMPERATURE FLOW
ATTACH A TEMPERATURE CLAMP TO THE FLOW PIPE
RESISTANCE HARNESS PUMP MODULATION
UNPLUG THE ELECTRICAL CONNECTOR FROM THE PUMP ASSEMBLY
RESISTANCE RETURN TEMPERATURE PROBE AND HARNESS
REMOVE 8 WIRE CONNECTOR FROM THE PCB
DISCONNECT EXTERNAL CONTROLS (TA1)
REMOVE CONNECTOR TA1 FROM THE PCB
ENSURE NO DEMANDS ARE PRESENT
INSPECTION FLOW METER MAGNET
ISOLATE THE COLD WAT
INSPECTION SILENCER
REMOVE THE SILENCER
INSPECTION AIR / GAS MIXER, BURNER AND HEAT EXCHANGER FLUEWAYS
REMOVE BURNER DOOR ASSEMBLY C/W FAN AND AIR / GAS MIXER
VOLTAGE STEPPER MOTOR
{GAINPCBACS}
RESISTANCE HARNESS DIVERTER MOTOR
DISCONNECT THE ELECTRICAL CONNECTOR FROM THE DIVERTER MOTOR
INSPECTION INTERNAL BYPASS
APPLIANCE DRAINED AN
INSPECTION CH FILTER
APPLIANCE DRAINED AN
VOLTAGE STEPPER MOTOR
{GAINPCBACS}
RESISTANCE HARNESS DIVERTER MOTOR
DISCONNECT THE ELECTRICAL CONNECTOR FROM THE DIVERTER MOTOR
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
REMOVE GAS VALVE CONNECTOR FROM THE PCB AND MAKE SAFE
PRESSURE GAS INLET DROP
ATTACH PRESSURE GAUGE TO GAS INLET PRESSURE TEST POINT
OBSERVATION SPARKING OCCURS
DISCONNECT THE IGNIT
RESISTANCE IGNITION ELECTRODE AND LEAD
REMOVE THE IGNITION ELECTRODE FROM THE BURNER DOOR
DISCONNECT THE IGNITION LEAD FROM THE PCB
INSPECTION AIR / GAS MIXER
REMOVE AIR / GAS MIXER (VENTURI)
INSPECTION BURNER AND SPARK GAP
THE BURNER DOOR ASSEMBLY SHOULD ALREADY BE REMOVED FROM PREVIOUS TEST
INSPECTION PRIMARY HEAT EXCHANGER FLUEWAYS
THE BURNER DOOR ASSEMBLY SHOULD ALREADY BE REMOVED FROM PREVIOUS TEST
RESISTANCE GAS VALVE AND HARNESS
REMOVE GAS VALVE CONNECTOR FROM THE PCB
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT
PRESSURE GAS INLET
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT
INSPECTION SILENCER
REMOVE THE SILENCER
PRESSURE EXPANSION VESSEL
APPLIANCE DRAINED AND DISCHARGED
RESISTANCE UNDERFLOOR HEATING THERMOSTAT
{GAINPCBACS}