Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature clamps to the flow and return pipes
If there is no access to remove the right hand side panel then you will need to use a temperature probe on the return pipe instead of a clamp
If there is no access to remove the right hand side panel then you will need to use a temperature probe on the return pipe instead of a clamp
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the appliance to run for central heating and the system to heat up.
Measure the temperature differential across the flow and return pipes.
Expect a temperature differential of approximately 20°C or less.
Measure the temperature differential across the flow and return pipes.
Expect a temperature differential of approximately 20°C or less.
Isolate as per TOPs P4
and refit as necessary