Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Attach a temperature clamp to the flow pipe
Remove silencer and attach a temperature clamp to the return pipe behind the fan
Refit the silencer
Note.
Ensure a good connection is made with the flow and return pipes or misdiagnosis will occur and ensure silencer is refitted before carrying out the test

WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow boiler to operate for hot water for 2 - 3 minutes.
Monitor the temperature differential across the flow and return pipes.
Expected a temperature differential of approximately 20°C or less.