Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Ensure hot water temperature control is set to MAX
Attach pressure gauge to gas valve pressure outlet test point
Disconnect the compensation pipe at the gas valve
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

1. Maximum burner pressure
Allow the boilers burner to ignite and establish.
Maximum burner pressure measured should be as per table 1.
2. Minimum burner pressure
Isolate Mains Power to appliance as per TOP's P4
Disconnect one lead to the gas valve modureg coil.
Mains power ON.
Allow the burner to ignite and establish.
Minimum burner pressure measured should be as per table 1.
Note: 1. Ensure a sufficient DHW flow rate to prevent boiler from modulating the burner pressure.