Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Remove 8 way connector from water sensor PCB

Measurement:

Measure for resistance across pins 1 & 2 of disconnected 8 way connector.
Although the condensate resistor is not a thermistor it does still have a negative temperature coefficient, as a result when the appliance combustion chamber is warmer the resistance measured will be lower and vice versa.
Expect a resistance between 170 kOhms and 400 kOhms.
The resistance measured should lie between these values relative to the appliance combustion chamber temperature.
Is resistance measured as expected?
Note:
Ensure a good connection is made as misdiagnosis will occur.