Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach FGA temperature clamp to the flow pipe
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset the boiler / cancel pump purge as necessary.
Run the appliance and allow the system to heat.
Monitor the boiler flow temperature.
The boiler flow temperature should reach approximately 80°C then maintain flow temperature or shut down without going to a temperature related fault code.
Note:
To speed up the process the heating load can be reduced by turning off some radiators.
Run the appliance and allow the system to heat.
Monitor the boiler flow temperature.
The boiler flow temperature should reach approximately 80°C then maintain flow temperature or shut down without going to a temperature related fault code.
Note:
To speed up the process the heating load can be reduced by turning off some radiators.