Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Ensure appliance is cool
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset the appliance by:
Turning the selector switch from CH/DHW position to the OFF/Reset position, wait a few seconds then turn the selector switch back to the CH/DHW position.
Apply a DHW demand.
Has the boiler reset?
Note:
It is important to apply a DHW demand after resetting.
Turning the selector switch from CH/DHW position to the OFF/Reset position, wait a few seconds then turn the selector switch back to the CH/DHW position.
Apply a DHW demand.
Has the boiler reset?
Note:
It is important to apply a DHW demand after resetting.