Set Appliance State:

Mains Power Off
Set Multimeter to AC Volts Set meter to measure AC Volts
Turn Hot Water Tap On
Selector switch set to CH/DHW position
Boiler DHW thermostat set to MAX
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow fan to run and ignition sequence to commence.
Measure the AC voltage between the gas valve modulating
solenoid terminals during the ignition phase.
Expect approximately 10 Vac.
Note:
The appliance may go to lockout, reset as required until the test is complete.