Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Hinge down the PCB
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Ensure all external controls are calling.
Measure for ac voltage across the two black terminals on terminal block (ME) as illustrated. (two connections left-hand side).
Expected voltage should be 0 volts.
Measure for ac voltage across the two black terminals on terminal block (ME) as illustrated. (two connections left-hand side).
Expected voltage should be 0 volts.

Isolate as per TOPs P4
and refit as necessary