Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
CH temperature control to max
Set selector switch to ch/dhw
Connect a U-gauge to the Burner Gas Pressure Test Point
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

CLICK HERE BEFORE CARRYING OUT THIS TEST
Allow the boiler to execute its ignition sequence and the burner to ignite.
Does the burner pressure operate between CH min and mix (refer to table) as the ch system temperature increases.
Note:
When gauge is removed pressure test point should be tightened and checked for gas tightness.