Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Remove connector M3 from the PCB
Remove connector M3 from the PCB
Measurement:
Note the operating pressure indicated on the pressure switch. Connect the air pressure switch charge test kit to the P1 connection on the air pressure switch.
Increase the pressure via the syringe to that indicated on the pressure switch.
Continuity / zero resistance should then be measured between the red and black pins on connector M3.
Notes:
If continuity / zero resistance is measured make a note of the pressure the switch operates at for use in the next test.
If continuity / zero resistance is not obtained, it is permissible to increase the pressure by 50%.
100 Pascals = 1mbar / 50 Pascals = 0.5mbar
Increase the pressure via the syringe to that indicated on the pressure switch.
Continuity / zero resistance should then be measured between the red and black pins on connector M3.
Notes:
If continuity / zero resistance is measured make a note of the pressure the switch operates at for use in the next test.
If continuity / zero resistance is not obtained, it is permissible to increase the pressure by 50%.
100 Pascals = 1mbar / 50 Pascals = 0.5mbar

Isolate as per TOPs P4
and refit as necessary