Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Ensure there is no demand for either CH or DHW
Use Insulation Mat as required
Gain access to the PCB
Gain access to the PCB
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage between X1 and X2 of the PCB.
Expect approximately 220V AC.
Expect approximately 220V AC.

Isolate as per TOPs P4
and refit as necessary