Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Remove the purple wires from the CH sensor
Remove the purple wires from the CH sensor
Measurement:
Measure the resistance across the terminals on the sensor.
The resistance measured will depend on boiler temperature.
The resistance measured will depend on boiler temperature.
| Temperature °C | Resistance in kOhms |
| 10-20 | 10.0-6.0 |
| 30-40 | 3.0-2.5 |
| 50-60 | 1.8-1.6 |
| 70-80 | 1.0-0.5 |

Isolate as per TOPs P4
and refit as necessary