Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove both ends of the flame sense harness, from the electrode and from X501 on the PCB
Measurement:
Measure the resistance of the flame sense harness lead.
Replace the harness after the test.
Expect continuity / zero resistance.
Is the resistance measured as expected?
Replace the harness after the test.
Expect continuity / zero resistance.
Is the resistance measured as expected?

Isolate as per TOPs P4
and refit as necessary